6-4
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
STATUS
CHAPTER 6: ACTUAL VALUES
6
6.3 Status
6.3.1 Motor
ACTUAL VALUES
STATUS
MOTOR
The
MOTOR STATUS
value reflects operating state of the motor.
The
MOTOR THERMAL CAPACITY USED
represents the thermal model accumulated thermal capacity used as a percentage
value.
The
ESTIMATED TRIP TIME ON OVERLOAD
value represents the estimated time to trip (in seconds) from the thermal model
assuming that the motor current remains at its current level. It is obtained from the thermal model curve and takes into
account that some percent of the thermal capacity has already been used.
The
THERMAL LOCKOUT TIME
reflects the calculated time required for the thermal capacity used to decay from its current
value to the level when thermal start inhibit is removed and new motor start is permitted. The
THERMAL LOCKOUT TIME
value displays only when the motor is offline. For details of lockout time calculations, see the Thermal Model section of
Chapter 5.
The
START/HOUR LOCKOUT TIME
,
TIME-BTWN-STARTS LO TIME
, and
RESTART DELAY LO TIME
lockout time values are calculated
from the Maximum Starting Rate, Time Between Starts, and Restart Delay elements, respectively.
The
TOTAL MOTOR LOCKOUT TIME
value is calculated as the maximum of all lockout times shown in this menu.
6.3.2 Contact inputs
ACTUAL VALUES
STATUS
CONTACT INPUTS
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
MOTOR
MOTOR STATUS:
Offline
MOTOR THERMAL
CAPACITY USED: 0%
ESTIMATED TRIP TIME
ON OVERLOAD: Never
THERMAL LOCKOUT
TIME: 0 min
START/HOUR LOCKOUT
TIME: 0 min
TIME-BTWN-STARTS LO
TIME: 0 min
RESTART DELAY LO
TIME: 0 s
TOTAL MOTOR LOCKOUT
TIME: 0 min
CONTACT INPUTS
Cont Ip 1
Off
Range: On, Off
Cont Ip xx
Off
Range: On, Off
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...