CHAPTER 5: SETTINGS
CONTROL ELEMENTS
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-293
5
5.8.7.3 Time between starts (ANSI 66)
SETTINGS
CONTROL ELEMENTS
START SUPERVISION
TIME BETWEEN STARTS
The time between starts element prevents restart attempts in quick succession. It requires that the minimum duration
specified by the
TIME BETWEEN STARTS MIN TIME
setting expires before a subsequent start attempt is allowed. The time
between starts supervising element complements the maximum starting rate element in that the former controls the time
spacing between starts and the latter limits the number of starts.
The element asserts the following three FlexLogic operands:
•
The
TIME-BTWN-STARTS PKP
operand indicates that the time since the last start was too short. When stopped, the motor
should not be restarted until the lockout time elapses.
•
The
TIME-BTWN-STARTS OP
operand indicates that the motor stopped when the time since the last start was too short.
Use this operand to inhibit the start command.
•
The
TIME-BTWN-STARTS DPO
operand indicates that the time between the last two starts was long enough. When
stopped, the motor can be restarted immediately.
The element uses motor status asserted by the Thermal Model element. The thermal protection must be configured
properly in order for this function to operate.
Figure 5-164: Time between starts logic
5.8.7.4 Restart delay
SETTINGS
CONTROL ELEMENTS
START SUPERVISION
RESTART DELAY
TIME BETWEEN
STARTS
TIME BETWEEN STARTS
FUNCTION: Disabled
Range: Disabled, Enabled
TIME BETWEEN STARTS
MIN TIME: 20 min
Range: 0 to 300 min. in steps of 1
TIME BWN STARTS BLK:
Off
Range: FlexLogic operand
TIME BETWEEN STARTS
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
TIME BETWEEN STARTS EVENTS:
Disabled
Range: Disabled, Enabled
RESTART DELAY
RESTART DELAY
FUNCTION: Disabled
Range: Disabled, Enabled
RESTART DELAY
MIN TIME: 0 s
Range: 0 to 50000 s in steps of 1
RESTART DELAY BLOCK:
Off
Range: FlexLogic operand
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...