6-22
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
METERING
CHAPTER 6: ACTUAL VALUES
6
If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display.
6.4.5 Tracking frequency
ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on configuration of the reference source. The
TRACKING FREQUENCY
is based on positive sequence current phasors from all line terminals and is synchronously adjusted
at all terminals. If currents are below 0.125 pu, then the
NOMINAL FREQUENCY
is used.
6.4.6 Frequency rate of change
ACTUAL VALUES
METERING
FREQUENCY RATE OF CHANGE 1(2)
The metered frequency rate of change for the frequency rate of change elements is shown here.
6.4.7 FlexElements
ACTUAL VALUES
METERING
FLEXELEMENTS
FLEXELEMENT 1(8)
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
SYNCHROCHECK 1
V1 MAG: 0.000 kv
SYNCHROCHECK 1
V1 ANG: 0.0°
SYNCHROCHECK 1
V2 MAG: 0.000 kV
SYNCHROCHECK 1
V2 ANG: 0.0°
SYNCHROCHECK 1 PROJ
V2 MAG: 0.000 kV
SYNCHROCHECK 1 PROJ
V2 ANG: 0.0°
SYNCHROCHECK 1 PROJ
DELTA_PHASE: 0.0°
SYNCHROCHECK 1 PROJ
SYNSCP D_PH: 0.0°
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
FREQUENCY RATE
OF CHANGE 1
FREQUENCY RATE OF
CHANGE1: 0.00 Hz/s
FLEXELEMENT 1
FLEXELEMENT 1
OpSig:
0.000
Base unit
Description
87L SIGNALS
(Local IA Mag, IB, and IC)
(Diff Curr IA Mag, IB, and IC)
(Terminal 1 IA Mag, IB, and IC)
(Terminal 2 IA Mag, IB and IC)
I
BASE
= maximum primary RMS value of the +IN and –IN inputs
(CT primary for source currents, and 87L source primary current for line differential currents)
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...