SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
Minimum load impedance:
Operate time:
< 0.6 ms
Internal Limiting Resistor:
100
Ω,
2 W
SOLID-STATE OUTPUT RELAY
Operate and release time:
<100 µs
Maximum voltage:
265 V DC
Maximum leakage current in off state
(excluding voltage monitor circuit current): 100 µA
Maximum continuous current:
5 A at 45°C; 4 A at 65°C
Make and carry:
for 0.2 s:
30 A as per ANSI C37.90
for 0.03 s:
300 A
Breaking capacity:
CONTROL POWER EXTERNAL OUTPUT (For dry contact input)
Capacity:
100 mA DC at 48 V DC
Isolation:
±300 Vpk
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k
Ω
for –1 to 1 mA range
12 k
Ω
for 0 to 1 mA range
600
Ω
for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change:
100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001
Input voltage Impedance
2 W Resistor
1 W Resistor
250 V DC
20 K
Ω
50 K
Ω
120 V DC
5 K
Ω
2 K
Ω
48 V DC
2 K
Ω
2 K
Ω
24 V DC
2 K
Ω
2 K
Ω
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load
impedance.
Specification
UL 508
Utility application
(autoreclose scheme)
Industrial application
Operations per
interval
5000 operations,
1 second on,
9 seconds off
5 operations
0.2 seconds on
0.2 seconds off
within 1 minute
10000 operations
0.2 seconds on
30 seconds off
1000 operations
0.5 seconds on,
0.5 seconds off
Break capability
(0 to 250 V DC)
3.2 A at L/R = 10 ms
10 A at L/R = 40 ms
10 A at L/R = 40 ms
1.6 A at L/R = 20 ms
0.8 A
L/R = 40 ms
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...