5-180
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
PMU 1 POWER TRIGGER ACTIVE
— Specifies the pickup threshold for the active power of the source. For single-phase power,
1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the
nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.
PMU 1 POWER TRIGGER REACTIVE
— Specifies the pickup threshold for the reactive power of the source. For single-phase
power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and
the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.
PMU 1 POWER TRIGGER APPARENT
— Specifies the pickup threshold for the apparent power of the source. For single-phase
power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and
the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator
applies a 3% hysteresis.
PMU 1 POWER TRIGGER PKP TIME
— Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.
PMU 1 POWER TRIGGER DPO TIME
— Use to extend the trigger after the situation returns to normal. This setting is of
particular importance when using the recorder in the forced mode (recording as long as the triggering condition is
asserted).
Figure 5-92: Power trigger logic
5.5.8.17 df/dt triggering
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PHASOR MEASUREMENT UNIT 1
PMU 1
TRIGGERING
PMU 1 df/dt TRIGGER
PMU 1 df/dt
TRIGGER
PMU 1 df/dt TRIGGER
FUNCTION: Disabled
Range: Enabled, Disabled
PMU 1 df/dt TRIGGER
RAISE: 0.25 Hz/s
Range: 0.10 to 15.00 Hz/s in steps of 0.01
PMU 1 df/dt TRIGGER
FALL: 0.25 Hz/s
Range: 0.10 to 15.00 Hz/s in steps of 0.01
PMU 1 df/dt TRIGGER
PKP TIME: 0.10 s
Range: 0.00 to 600.00 s in steps of 0.01
PMU 1 df/dt TRIGGER
DPO TIME: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PMU 1 df/dt TRG BLK:
Off
Range: FlexLogic operand
PMU 1 df/dt TRIGGER
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...