CHAPTER 5: SETTINGS
SYSTEM SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-147
5
These settings ensure that the 87L element correctly applies magnitude and phase compensation for the in-zone
transformer. To accommodate for the difference in CT ratios at line terminals, use the
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE DIFFERENTIAL ELEMENTS
CURRENT DIFFERENTIAL
CURRENT DIFF CT TAP
setting. It is important
to properly program the in-zone transformer setting for all terminals to ensure correct 87L performance.
IN-ZONE TRANSFORMER CONNECTION
— This setting indicates the presence and group connection of the in-zone
transformer. The winding angle selection specifies the phase shift of the remote terminal side winding with respect to the
local terminal side winding. For example, for the Dy1 group where the delta winding is connected to the local terminal side,
and wye winding is connected to the remote terminal side, you select “30° lag” for the local terminal side. (At the remote
terminal relay, select “330° lag” for this transformer group connection.) If there is no in-zone transformer connected, then
program this setting as “None” (note that the “0° lag” value does not correspond to “None”). Only one in-zone transformer
is allowed for both two-terminal and three-terminal applications. Enabling in-zone transformer functionality forces the L30
to automatically remove the zero-sequence component from all terminals currents. It also disables ground differential
87LG functionality and zero-sequence current removal functionality defined by the
ZERO SEQ CURRENT REMOVAL
setting.
Do not set the
IN-ZONE TRANSFORMER CONNECTION
setting to "None" at one terminal and set other terminals to a value
other than "None." 87L is blocked under these circumstances.
TRANSFORMER LOCATION
— This setting selects the transformer location and applies only when the
IN-ZONE TRANSFORMER
CONNECTION
setting is other than “None.”
Select the “LOCAL-TAP” value if the transformer is present between the local terminal and the tap point or for two-terminal
applications.
Select “REM1-TAP” if the transformer is present between remote terminal 1 and the tap point.
Select “REM2-TAP” if the transformer is present between remote terminal 2 and the tap point.
Figure 5-64: Illustration of in-zone transformer for two-terminal and three-terminal lines
5.5.5 Breakers
SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(2)
TRANSFORMER LOCATION:
LOCAL-TAP
Range: LOCAL-TAP, REM1-TAP, REM2-TAP
The L30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...