KVCG202/EN M/H11
Technical Manual
KVGC202
9.8.5.2 Relay no longer responding
Check if other relays that are further along the bus are responding and if so, power down
the relay for 10 seconds and then re-energise to reset the communication processor. This
should not be necessary as the reset operation occurs automatically when the relay
detects a loss of communication.
If relays further along the bus are not communicating, check to find out which are
responding towards the master station. If some are responding then the position of the
break in the bus can be determined by deduction. If none is responding then check for
data on the bus or reset the communication port driving the bus with requests.
Check there are not two relays with the same address on the bus.
9.8.5.3 No response to remote control commands
Check that the relay is not inhibited from responding to remote commands by observing
the system data function link settings. If so reset as necessary; a password will be
required.
System data function links cannot be set over the communication link if the remote
change of settings has been inhibited by setting system data function link [0003 SD Links]
link 1 to “0”. Reset [0003 SD Links] link 1 to “1” manually via the user interface on the
relay first.
Relay does not respond to load shedding/boosting levels set from the courier master
station. Check input masks settings to ensure the load shedding/boosting is not selected
by the opto inputs as this will override the commands over the serial port.
9.8.6
Output relays remain picked-up
Relays remain picked-up when de-selected by link or mask.
If an output relay is operated at the time it is de-selected, either by a software link change
or by de-selecting it in an output mask, it may remain operated until the relay is powered
down and up again. It is therefore advisable to momentarily remove the energising supply
after such changes.
9.8.7
Measurement accuracy
The values measured by the relay can be compared with known system values to check
that they are approximately within the tolerance given below. If they are not then the
following can be tried:
-
Reset the relay by removing the auxiliary supply for 10 seconds
-
Recalibrate the relay
If problem is still not solved, then the relay should be returned to the factory.
The measurements should be within the following tolerance:
Measurements
Tolerance
Load current
±2%
Circulating current
±5%
Measured Voltage
±2%
Regulated Voltage
±0.5% of system voltage
Frequency
±1%
Timing measurements
±0.5% or 15 to 35ms (Definite time)
±10% (Inverse time)
9.9
Maintenance
K Range Midos relays are self-supervising and so require less maintenance. Most
problems will result in an alarm so that remedial action can be taken. However, some
periodic tests could be conducted to ensure that the relay is functioning correctly.
Содержание KVGC 202
Страница 2: ......
Страница 10: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 122: ...KVCG202 EN M H11 Technical Manual KVGC202 Figure 36 Test circuit diagram ...
Страница 123: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 1 ...
Страница 124: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 125: ...Technical Manual KVCG202 EN M H11 KVGC202 Figure 37 Relay inverse time characteristic curve ...
Страница 126: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 127: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 2 ...
Страница 128: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 129: ...Technical Manual KVCG202 EN M H11 KVGC202 ...
Страница 130: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 131: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 3 ...
Страница 132: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 133: ...Technical Manual KVCG202 EN M H11 KVGC202 W02474 10 KVGC202 00 SHEET 1 ...
Страница 134: ...KVCG202 EN M H11 Technical Manual KVGC202 W02475 10 KVGC202 00 SHEET 2 ...
Страница 135: ...Technical Manual KVCG202 EN M H11 KVGC202 W02476 10 KVGC202 00 SHEET 3 ...
Страница 136: ...KVCG202 EN M H11 Technical Manual KVGC202 W02477 10 KVGC202 00 SHEET 4 ...
Страница 137: ...Technical Manual KVCG202 EN M H11 KVGC202 W02478 10 KVGC202 00 SHEET 5 ...
Страница 138: ...KVCG202 EN M H11 Technical Manual KVGC202 W02479 10 KVGC202 01 SHEET 1 ...
Страница 139: ...Technical Manual KVCG202 EN M H11 KVGC202 W02480 10 KVGC202 01 SHEET 2 ...
Страница 140: ...KVCG202 EN M H11 Technical Manual KVGC202 W02481 10 KVGC202 01 SHEET 3 ...
Страница 141: ...Technical Manual KVCG202 EN M H11 KVGC202 W02482 10 KVGC202 01 SHEET 4 ...
Страница 142: ...KVCG202 EN M H11 Technical Manual KVGC202 W02483 10 KVGC202 01 SHEET 5 ...
Страница 143: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 4 ...
Страница 144: ...KVCG202 EN M H11 Technical Manual KVGC202 ...