KVCG202/EN M/H11
Technical Manual
KVGC202
9.6
Control functions
Reference should be made to Appendix 3 for the application diagram used for the
following tests. The relay should be commissioned with the settings calculated for the
application.
9.6.1
Regulated Voltage setting V
S
and Dead Band dV
S
The relay should be commissioned with the settings calculated for the application.
This test checks the function of the transformer tap change control. The relay
continuously monitors the system voltage and compares it with the reference voltage Vs.
If the regulated voltage moves outside the deadband limits the relay actuates the tap
changer mechanism to ‘Raise’ or ‘Lower’ the voltage to bring it back within the set
deadband limits after the initial set time has elapsed.
[Before making the following changes note the settings for: Initial time delay (tINIT), inter-
tap delay (tINTER) setting, and Initial time characteristic.
Set the initial time delay (tINIT) and the inter-tap delay (tINTER) to 0 seconds for
continuous tap change.
Set the definite/inverse time characteristic to ‘definite time’].
Monitor ‘Raise volts’, ‘Lower volts’ and ‘Blocked’ relay contacts.
Energise the auxiliary voltage supply and check that ‘Blocked’ is displayed on the LCD
and ‘Blocked’ relay contact is closed.
Apply the system voltage and adjust the voltage equivalent to the system voltage setting
(Vs) to (terminals 17 and 18). The ‘CONTROL’ LED should extinguish, and the
raise/lower volts relay contacts should become open.
Slowly increase the supply voltage and record the voltage (V
HIGH
) at which the ‘Lower
volts’ contacts closes. The ‘CONTROL’ LED should illuminate. Reduce the supply
voltage until ‘CONTROL’ LED extinguishes again.
Slowly reduce the voltage further and record the voltage (V
LOW
) at which the raise volts
contacts ‘Raise volts’ closes. The ‘CONTROL’ LED should illuminate.
Using the values recorded for V
HIGH
and V
LOW
, calculate the regulated value Vreg and
the actual deadband as follows:
Vreg = (V
HIGH
+ V
LOW
)/2
dVs
actual
= (V
HIGH
– V
LOW
)
The value of Vreg should be (Vs ±0.5%) and the deadband should (dVs ±0.5% of Vs).
[Restore all settings changed i.e. the initial time delay, the inter-tap delay, and the initial
time characteristic.]
9.6.2
Load shedding/boosting
The relay should be commissioned with the settings calculated for the application only
check for the settings levels used for this application.
The purpose of this test is to ensure that the level of load shedding function is working.
The system voltage setting (Vs) can be raised or lowered by means of load shedding
option.
[Before making the following changes note the setting for: input masks, inter-tap delay
(tINTER) setting.
Set the inter-tap delay (tINTER) to 0 seconds
For this test ensure that the input masks are set to operate the following opto inputs
[0707, 0708, 0709 INPUT MASKS]:
For test 1 and 4 connect L0 OPTO (terminal 46) to switch S1.
For test 2 and 5 connect L1 OPTO (terminal 48) to switch S1.
Содержание KVGC 202
Страница 2: ......
Страница 10: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 122: ...KVCG202 EN M H11 Technical Manual KVGC202 Figure 36 Test circuit diagram ...
Страница 123: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 1 ...
Страница 124: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 125: ...Technical Manual KVCG202 EN M H11 KVGC202 Figure 37 Relay inverse time characteristic curve ...
Страница 126: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 127: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 2 ...
Страница 128: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 129: ...Technical Manual KVCG202 EN M H11 KVGC202 ...
Страница 130: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 131: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 3 ...
Страница 132: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Страница 133: ...Technical Manual KVCG202 EN M H11 KVGC202 W02474 10 KVGC202 00 SHEET 1 ...
Страница 134: ...KVCG202 EN M H11 Technical Manual KVGC202 W02475 10 KVGC202 00 SHEET 2 ...
Страница 135: ...Technical Manual KVCG202 EN M H11 KVGC202 W02476 10 KVGC202 00 SHEET 3 ...
Страница 136: ...KVCG202 EN M H11 Technical Manual KVGC202 W02477 10 KVGC202 00 SHEET 4 ...
Страница 137: ...Technical Manual KVCG202 EN M H11 KVGC202 W02478 10 KVGC202 00 SHEET 5 ...
Страница 138: ...KVCG202 EN M H11 Technical Manual KVGC202 W02479 10 KVGC202 01 SHEET 1 ...
Страница 139: ...Technical Manual KVCG202 EN M H11 KVGC202 W02480 10 KVGC202 01 SHEET 2 ...
Страница 140: ...KVCG202 EN M H11 Technical Manual KVGC202 W02481 10 KVGC202 01 SHEET 3 ...
Страница 141: ...Technical Manual KVCG202 EN M H11 KVGC202 W02482 10 KVGC202 01 SHEET 4 ...
Страница 142: ...KVCG202 EN M H11 Technical Manual KVGC202 W02483 10 KVGC202 01 SHEET 5 ...
Страница 143: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 4 ...
Страница 144: ...KVCG202 EN M H11 Technical Manual KVGC202 ...