12
KSA700 Series User Guide
To re-activate the keyboard a level 2 access password must be entered (see section 2.3
Access levels and passwords).
3.2.4.4 Delayed mode
A time delay can be programmed in any zone for daylight hours or for a specified period
of the day. It may only be programmed in access level 3 (i.e. by the installer) but can be
disabled and enabled as required from access level 2.
Delay modes allow the user to verify the cause of the alarm before outputs (relays and
sounders) are activated.
When this option is enabled the corresponding LEDs of the front panel are switched on.
When the fire panel detects a fire and a delay has been programmed only the fire panel
internal buzzer is activated. Through the LCD display and corresponding LEDs, the
system informs the operator about the device that originated the alarm and that the
system is in the first phase of a delayed alarm.
By pressing the
Silence Buzzer
or
Mute
key, the system moves into the second delayed
alarm phase, normally programmed to be long enough to allow confirmation of the cause
of the alarm and apply the appropriate corrective actions.
If the Silence Buzzer key is NOT pressed, the system moves into the confirmed alarm
mode.
The fire panel must be
Reset
before the programmed delay for phase 2 has expired, else
the confirmed alarm will be triggered.
"
Manual call points always trigger a confirmed alarm situation as no delay is
allowed.
When
Delayed Mode
is selected, the system asks for the number of days that this delay
mode should be active. Using the
Change
or
*
keys enter the required number. Once
activated, the Delayed Mode LED is switched on.
"
To enable the delay mode permanently, enter 200 days.
3.2.4.5 Relay / Sounders
This option is useful to check the system without releasing the sounders and outputs.
Select
Relay / Sounders
from the
Disable Menu
and select the item to be disabled from
the following screen.
1.
Sounders [Enabled]
2. Relays
[Enabled]
An access level password is requested to complete this option and a confirmation screen
details the event.