INSTALLATION INSTRUCTIONS

(continued)

8

Plan the Ductwork

1.

This downdraft blower system is designed

for use with 3

1

4

x 10

ductwork (can be transitioned

to 6

round). Three different discharge

directions are available with side--to-side
adjustment for accurate alignment of ductwork.

2. 

For best performance: Choose the ducting

option which allows the shortest length of
ductwork and a minimum number of elbows and
transitions. Check location of floor joists, wall
joists, wall studs, electrical wiring or plumbing
for possible interference.

NOTE: 

The unit is shipped with the 3

1

4

x 10

discharge facing DOWN. See the Changing
Blower Direction section, if necessary.

Steps to Determine Flexible Ducting’s
Equivalent Length

1. 

Measure the actual amount of offset

(Maximum 3

recommended). The effect upon

airflow is dependent upon the amount of offset.

2. 

Calculate the equivalent ducting allowances

using:

( ___ in. offset) x (14 Ft. per inch) 
= ___ Ft. equivalent length.

3. 

Ensure that the total equivalent length of

ducting does not exceed the maximum
recommendation of 100 feet.

Right
discharge

Down discharge
(as shipped)

Left discharge 

Duct Pieces

Equivalent Length*

Duct Pieces

Equivalent Length*

3

1

4

x 10

″ 

6

Round

to 6

Round

5 ft.

Straight

1 ft. (per foot length)

Transition

6

Round

to 3

1

4

x 10

3

1

4

x 10

1 ft. (per foot length)

Transition

20 ft.

Straight

90° Elbow

3

1

4

x 10

to 6

Round

6

15 ft.

Transition

12 ft.

90° Elbow

90° Elbow

6

Round

6

Wall Cap

21 ft.

45° Elbow

9 ft.

with Damper

3

1

4

x 10

3

1

4

x 10

Wall Cap

27 ft.

90° Elbow

16 ft.

with Damper

3

1

4

x 10

6

Round

45° Elbow

5 ft.

Roof Cap

20 ft.

3

1

4

x 10

6

Round

90° Flat Elbow

24 ft.

Roof Vent

24 ft.

6

Round

to 3

1

4

x 10

7 ft.

Transition

SHOULD NOT EXCEED 100 EQUIVALENT FT.
*Equivalent lengths of duct pieces are based on actual tests conducted by

GE Evaluation Engineering and reflect requirements for good venting
performance with a downdraft rated at 500 CFM.

29

1

/

2

Venting Island to Outside Wall

Wall

7

24

Power

Cord provided
(on-right-hand side)

Содержание JVB34

Страница 1: ...ctions 2 Operating Instructions Tips Canning 3 Controls 3 Cooking Tips 3 Care and Cleaning Blower 4 Grease Filter 4 Problem Solver 4 More questions call GE Answer Center 800 626 2000 Installation 5 11 Ductwork Table 8 Plan Ductwork 8 Plan Wiring 9 Install Ductwork 10 Install Wiring 10 Consumer Services Warranty Back Cover ...

Страница 2: ... FOLLOWING A SMOTHER FLAMES with a close fitting lid cookie sheet or metal tray then turn off the burner BE CAREFUL TO PREVENT BURNS If the flames do not go out immediately EVACUATE AND CALL THE FIRE DEPARTMENT B NEVER PICK UP A FLAMING PAN You may be burned C DO NOT USE WATER including wet dishcloths or towels a violent steam explosion will result D Use an extinguisher ONLY if 1 You know you have...

Страница 3: ... the activating switch again The air vent will go down and the blower will shut off NOTE For most convenient operation set the blower to your favorite speed The blower will come on to this speed whenever the activating switch is pressed and the air vent rises Safety Instructions Servicing Using Vent System Cooking Tips Knob COOKING TIPS The high capacity performance of this downdraft system can in...

Страница 4: ...FT POWER SUPPLY BY REMOVING THE POWER CORD FROM THE RECEPTACLE 2 Remove the blower cover 3 Use a vacuum hose to clean the blower Do not immerse the blower in water 4 Replace the blower cover 5 Reconnect the power supply Clean greasy surfaces frequently using a mild detergent Do not use abrasive cloth steel wool pads or scouring powder because they will mar the surface Stainless Steel on some model...

Страница 5: ...es Install a standard wiring box with a 3 pronged outlet Plan the location of the gas supply pipe for gas cooktops carefully to avoid interference with the downdraft installation Specifications This unit can be easily installed following these basic steps Cut out the countertop opening Install the downdraft in the cabinet Connect the ductwork and electrical Install the cooktop VOLTS AMPS CFM DUCT ...

Страница 6: ...Depth Front Edge Min Req d Cooktop Cooktop Add l Depth Cutout Width Overall Overall Vent Cktop Cntrtop to Front Inside Cabinet Cutout Cutout Req d for Req d from Model No Width Depth Depth D D Vent Edge of Cutout Clearance Width Depth Downdraft Centerline JP300 JP301 JP310 30 1 4 21 1 4 2 23 1 4 3 1 2 22 28 1 2 19 1 2 2 7 8 27 1 16 JP311 JP325 JP332 JP333 30 21 2 23 3 1 4 22 28 1 2 19 1 2 2 5 8 27...

Страница 7: ...re 3 Figure 3 Min Setback Downdraft Cooktop Cooktop Depth Front Edge Min Req d Cooktop Cooktop Add l Depth Cutout Width Overall Overall Vent Cktop Cntrtop to Front Inside Cabinet Cutout Cutout Req d for Req d from Model No Width Depth Depth D D Vent Edge of Cutout Clearance Width Depth Downdraft Centerline JP622 JP623 35 1 2 21 2 23 3 1 4 22 33 7 8 19 1 16 2 7 8 33 1 16 JP681 35 1 2 21 2 23 3 1 4 ...

Страница 8: ...s using ___ in offset x 14 Ft per inch ___ Ft equivalent length 3 Ensure that the total equivalent length of ducting does not exceed the maximum recommendation of 100 feet Right discharge Down discharge as shipped Left discharge Duct Pieces Equivalent Length Duct Pieces Equivalent Length 31 4 x 10 6 Round to 6 Round 5 ft Straight 1 ft per foot length Transition 6 Round to 31 4 x 10 31 4 x 10 1 ft ...

Страница 9: ...able or work surface DOWN DISCHARGE Moving Blower Left or Right 1 Loosen the 4 nuts and 2 clamp channels 2 Slide the blower to the desired position 3 Use the supplied cover plate to close the open space if any 4 Tighten the nuts to secure the top of the blower and use the sheet metal screws through the bottom flange to secure the bottom of the blower Nuts Clamp channel Bottom flange Blower Sheet m...

Страница 10: ...r cable into the cabinet and connect it to the outlet 3 Plug the downdraft s power cord into the outlet Install the Ductwork CAUTION BEFORE CUTTING A HOLE IN CABINET FOR DUCTWORK Check for interference with floor joists wall studs electrical wiring or plumbing 1 Cut the hole in the cabinet as well as holes in the wall or floor as necessary 2 Mount the roof or wall cap and work back towards the cab...

Страница 11: ...ng switch just comes in contact with the underside of the switch membrane Tighten the screws 5 Replace the switch cover gently lower the air vent into the chimney and plug in the power cord Re connect the electrical power and check operation WARNING To avoid possible electrical shock personal injury or death disconnect electrical power Install the Cooktop 1 Align the cooktop with the downdraft and...

Страница 12: ...per installation If you have an installation problem contact your dealer or installer You are responsible for providing adequate electrical exhausting and other connecting facilities as described in the Installation Instructions provided with the product Replacement of the replaceable filters Replacement of house fuses or resetting of circuit breakers Failure of the product if it is used for other...

Отзывы: