Installation of the range.
Read these instructions completely and carefully.
3-Wire Conduit Installation
Remove the 3 screws from the connector block.
Insert bare wires between the connector block
terminals and movable nuts. Tighten screws
securely. Do not remove ground strap
connection.
WARNING:
Connector block is
approved for copper wire connection only. If
aluminum wire is used, see note below.
NOTE:
ALUMINUM WIRING
Do not connect aluminum wire to the
connector block.
Use copper building wire rated for the
correct amperage and voltage to make 3
(three) 3
″
copper jumper wires. Connect
wire as per Step 4 or 5 depending on number
of wires.
Splice copper wires to aluminum wiring
using special connector terminals designed
and UL-approved for joining copper to
aluminum and follow the connector
manufacturer’s recommended procedure
closely.
Wire used, location and enclosure of splices, etc., must
conform to good wiring practices and local codes.
Screw
Flexible cable
Bare wire
Movable nut
Connector
block terminal
Bare wire tips
Conduit
Connector block
Bracket