Pulsar Controller Status
Display
Millennium Controller
Status Display
Rect/
Conv
LEDs
Dist.
Module
LED
Possible Problem(s)
Possible Solution(s)
MAJ Multiple Rectifier
Fail,
MAJ Battery on
Discharge
Fail
red
(multiple
Units)
green
Multiple rectifier outputs have
dropped below 18V (36V); rectifiers
have shut down
.
1. Reset the rectifiers by removing the rectifiers, waiting
approximately 30 seconds, and replacing the rectifiers.
2. If problem not corrected, replace rectifiers.
•
Excessive ambient temperature;
multiple rectifiers have shut
down
•
Multiple rectifiers have failed.
1. Verify that there is no obstruction of the vertical airflow path
and fans are turning.
2. Reset rectifies by removing them, waiting approximately 30
seconds, and replacing them.
3. If problem persists, replace the rectifiers.
4. If problem persists, call your local field representative.
Fail
red
(all
Units)
green
•
All rectifier outputs have dropped
below 18V (36V); all rectifiers
have shut down
•
Defective controller.
1. Remove controller and reset the rectifiers by removing the
rectifiers, waiting approximately 30 seconds, and replacing the
rectifiers.
2. If output voltage does not go to set-point previously set by user,
call your local field representative.
MAJ High Voltage
Fail
red
(multiple
Units)
green
•
High output voltage from
rectifier(s).
•
Rectifier(s) high voltage shut
down
•
Internal rectifier(s) failure.
•
VHV threshold set below float set
point.
1. Check and adjust VLV threshold to above float set point.
2. Reset the rectifier(s) by removing the rectifier(s), waiting
approximately 30 seconds, and replacing the rectifier(s).
3. If problem persists, replace rectifier(s).
4. If problem persists, call your local field representative.
32
When a power unit senses an over- or under-voltage condition it will shutdown, wait 10 seconds, and then attempt to restart. If the over- or under-voltage condition remains it
will cycle again. If the over- or under-voltage condition remains after 3 restart attempts the power unit will lock out, and user intervention is required to restart.
BD AC DC
red green green
-54.48V1 1000A
FLOAT
Display Red
Minor
Rectifier/
red
Converter
amber
green green green
BD AC DC
-54.48V1 1000A
FLOAT
Display Red
Minor
Rectifier
red
amber