NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
25
Step
Action
Figure 23 Breaker Panel Alarm Connections
Connect Breaker Panel Alarms
Each Breaker panel has FAJ Faston® connections on the left side of the panel.
Single voltage panels have a either a 24V or a 48V FAJ pin and the selectable panel (if present) has both.
Alarms for the Primary voltage in the both frames should be factory jumpered together.
7
a.
Verify that all supplemental frame breaker panel Primary voltage FAJ alarms are jumpered together.
b.
Connect them to the same FAJ connection on the initial frame (white wire).
8
Connect Secondary voltage FAJ alarm from supplemental frame breaker panel to the same FAJ connection in
the Initial frame (yellow wire).
To next panel or to Frame FAJ
24V FAJ
To next panel or to Frame FAJ
48V FAJ