GEK-49950
H IGH- SE I SM IC TARGET AND SEAL- IN UN IT
Rati ngs for the target and seal-in u n it are show n in Tabl e V I I.
TABLE V I I
Tap
RATINGS PARAMETER
0.2
2
DC Resistance,
+
8.0
0.24
Min. Operati ng Current, amperes
+
0
0.3
2.0
Carry Conti nuous Current, amperes
0.3
3
Carry 30 Amperes
0.3
4
Carry 10 Amperes
0.25
30
60 Hertz
68.6
0.73
I f the trip pi n g cu rrent ex ceeds 3 0 a m peres, an a ux il ia ry rel ay should b e u sed and
con nections a rranged such that the trip ping cu rrent does not p ass th roug h the contacts o r
the target and seal- i n coils of the protective rel ay.
CONTACT S
The cu rrent-closing rating o f the contacts i s 30 amperes for voltages not exceed ing 25 0
volts. The current-carrying rating is l i m ited b y the rating of the seal- i n u n it.
BURDENS
Bu rdens for the time-overcu rrent u n it a re g iven i n T able V I I I.
N OTE:
T he i m pedance valu es g iven i n T able V I I I a re those for the m i n i m u m tap o f each
range; the i m pedance for oth er ta ps at pick u p cu rrent (ta p rati n g) va ries
inversely (approx i mately) as the sq uare of the tap rating. For ex a m pl e a n I FC95
60 h ertz rel ay w ith 1 - 12 amp range has an i m pedance of 6.27 oh ms on the 1.0
a m p tap. T he i mpedance of the 2.0 amp tap is (1.0/2.0)2 x 6.27
=
1.57 o h ms.
7