GE IC695ETM001 Скачать руководство пользователя страница 14

14 

RX3i Ethernet Interface Module IC695ETM001-HV IPI 

GFK-2332W 

February 2016 

 

Ethernet Operational Notes 

Subject 

Description 

Configuration of IP Address is 

required before using Ethernet 

communications 

The Ethernet Interface cannot operate on a network until a valid IP 

address is configured. The Ethernet addressing information must be 

configured prior to actual network operation, or to recover from 

inadvertent changes to the Ethernet addressing data at the Ethernet 

Interface. Use one of the following methods to initially assign an IP 

address: 

 

Connect a serial terminal to the Interface’s Station Manager port. 

Then use the CHSOSW command to enter the desired IP address. For 

details, see PACSystems TCP/IP Communications Station Manager 

Manual, GFK-2225. 

 

Temporarily assign an IP address to the module using the SetIP tool 

over the Ethernet network. For details, see 

TCP/IP Ethernet 

Communications for PACSystems

, GFK-2224. 

 

The Ethernet Interface automatically obtains a temporary IP Address 

from a BOOTP server on the network. For details, see 

TCP/IP Ethernet 

Communications for PACSystems,

 GFK-2224. 

Once a temporary IP address has been set up, the Ethernet Interface can 

be accessed over the network (by the Machine Edition programming 

software). The programmer should then be used to configure the proper IP 

address for the Ethernet Interface. 

Default IP address (0.0.0.0) 

attempts to set IP address 

via BOOTP 

The default IP address value (0.0.0.0), whether obtained from HW 

Configuration or backup configuration, causes the Ethernet Interface to 

request a temporary IP address from a BOOTP server device on the 

network. 

LAN must be tree, not ring 

The two Ethernet network ports on the PACSystems RX3i Ethernet 

Interface must not be connected, directly or indirectly, to the same 

network device.  The hub or switch connections in an Ethernet network 

must form a tree and not a ring; otherwise duplication of packets and 

network overload may result. In this situation, the RX3i Ethernet modules 

will continually reset. 

Reporting of duplicate IP 

address 

The PACSystems RX3i does not log an exception or a fault in the Controller 

Fault Table when it detects a duplicate IP address on the network.   

Multiple zero period EGD 

exchanges may not produce 

similar numbers of samples 

If more than one EGD produced exchange is configured for a production 

period of zero, the exchanges may not produce similar numbers of 

samples.  Due to the way that scheduling occurs when multiple 

exchanges are scheduled “as fast as possible”, some zero period 

exchanges may produce significantly more samples than others. For more 

consistent EGD production, configure the produced EGD exchanges with 

non-zero production periods. 

Changing IP address while 

SRTP connection open may 

generate log events 

Open SRTP Server connections established with a remote SRTP client are 

not terminated as expected when the RX7i’s IP address is changed 

(typically by storing a new HW Configuration to the RX7i).  A Series 90 SRTP 

client (“SRTP channels”) reports either a 9690H or 0190H status; the SRTP 

connection may remain open until the connection is terminated as a result 

of a client timeout.  Please refer to 

Open Ethernet Problems,

 Internal 

Problem ID Code CR-1434 for more information. 

Series 90-30 datagram 

restrictions 

Series 90-30 – format datagrams are supported, but cannot access %P or 

%L memory.  

 

Содержание IC695ETM001

Страница 1: ... Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded twisted pair Ethernet ports for direct connection to either a 10BaseT or 100BaseTX IEEE 802 3 network without an external transceiver There is only one interface to the network only one Ethernet MAC addres...

Страница 2: ...tion Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redunda...

Страница 3: ...l ETHERNET OK LAN OK LOG EMPTY Blink error code Off Off Hardware failure See chapter 11 for blink code definitions ETHERNET OK LAN OK LOG EMPTY Slow Blink Slow Blink Slow Blink All LEDs blink in unison pattern same while awaiting or performing load Firmware Update Field Wiring Station Manager RS 232 Port Pin Assignment Pin No Signal Direction Description 1 DCD IN Data Carrier Detect 2 TX OUT Trans...

Страница 4: ...he enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of...

Страница 5: ...odule to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket into threaded holes in the bottom of the backplate and screw them several turns using a 1 Phillips screwdriver Tighten to 0 7 N m 6 in lbs Related Documents For additional information about the Ethernet Interface Module refer to the following publications GFK 2314 PACSystems R...

Страница 6: ...d LAN Interface IC693CPU364 and IC693CPU374 like any Series 90 30 CPU should not be placed in an RX3i rack Modbus TCP support Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channels capability It supports Modbus Conformance Class 0 function codes 3 and 16 Conformance Class 1 function codes 1 2 4 5 6 and 7 and Conformance Class 2 function codes 15 22 23 and 24 PACSystems E...

Страница 7: ...to the supplied value Release History Release History Catalog Number Firmware Version Date Comments IC695ETM001 HV 6 40 Feb 2016 An enhancement was made to prevent the module from becoming unresponsive and requiring a power cycle if it was subjected to heavy network storm traffic Reference GE Security Advisory is GE15 09 titled Network Storm Denial of Service In addition to the enhancement there w...

Страница 8: ... change to the module s firmware or functionality IC695ETM001 ES 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled IC695ETM001 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 7 IC695ETM001 EP 6 14 Jul 2012 Resolves an issue with a spur...

Страница 9: ...he connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection i...

Страница 10: ...ault can be safely ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout er...

Страница 11: ...eference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink ...

Страница 12: ...o the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir1 and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4...

Страница 13: ...s is disabled until the station manager password is changed to other than the default password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K Changing the default Station Manager password is strongly recommended GE Intelligent Platforms strongly recommend...

Страница 14: ...ress from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ether...

Страница 15: ...ntain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeo...

Страница 16: ...net interface time via the CHTIME command does not affect the timestamp value within EGD exchanges produced from this Ethernet interface The EGD timestamp value reflects the current CPU time In Series 90 70 products and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run Mode Store of EGD In a large PPS system ...

Отзывы: