ADJUSTABLE FEATURES
SX TRANSISTOR CONTROLS
Page
33
(Push CONT 8)
This function is used to reduce the ripple in field current
due to the interaction between motor field design and the
digital field current regulation circuit. The value for this
function should be set to 0.
Important Note: The function is used to optimize motor and
control performance and this setting will be determined by
GE and OEM engineers at the time of vehicle development.
This setting must not be changed by field personnel without
the permission of the OEM.
FIELD WEAKENING START (or MOTOR
FUNCTION 24
KNEE POINT)
This function allows for setting the armature current at
which minimum field current will be achieved.
0 to 255Amps
Range
0 to 255
Setting
1.0 per set unit
Resolution
Setting of 26 = 26 amps.
Example:
Important Note: The function is used to optimize motor and
control performance and this setting will be determined by
GE and OEM engineers at the time of vehicle development.
This setting must not be changed by field personnel without
the permission of the OEM.
FUNCTION 25
NOT USED
Value should be set at zero.
FUNCTION 26
RATIO OF FIELD TO ARMATURE AMPS
This function sets the ratio between armature and field
current when transitioning from minimum field to maximum
field current. The setting represents the quantity of field
current changed for each 1 amp of armature current
changed.
Example
Resolution
Max
Set
If set at 100
Per unit value
Change
0.072 amps
0.00072 amps
0 to 255
.18
FUNCTION 27
HOUR METER MINUTES
This function adjusts the number of 30 second intervals
registering in the hour meter. This function is typically not
set by an OEM, it is usually only read from the register.
Range
0 to 60 minutes
0.5 minutes per set unit
Resolution
0 to 120
Setting
Setting of 60 = 60 x 0.5 = 30 minutes
Example
STORED STATUS CODE COUNT
FUNCTION 28
POINTER
This register contains the location of the last stored status
code recorded of the 16 stored status codes. These stored
status codes have caused a PMT controller shutdown
and/or disruption of normal vehicle operation.
HOUR METER TENS AND UNITS
FUNCTION 29
HOURS
SET
This function allows for the adjustment of the tens and
units hours of the hour meter.
Range
0
to
99
0
to
99
Set
9999
Example
Hours
HOUR METER THOUSANDS
FUNCTION 30
AND HUNDREDS HOURS SET
This function allows for the adjustment of the thousands
and hundreds hours of the hour meter.
Range
0
to
99
Set
0
to
99
Example
9999 Hours