ADJUSTABLE FEATURES
SX TRANSISTOR CONTROLS
Page 58
October 1998
FUNCTION 51
MODE 1 RATIO
(Push
CONT
4)
This function sets the ratio between armature and field
current when transitioning from minimum field to maximum
field current. The setting represents the quantity of field
current changed for each 1 amp of armature current
changed.
Max
Fld Ref
Max
Change
Set
Resolution
Per Unit Value
Example
If Set at 5
20
.24
0 to 10
0.024
0.12 amps
30
.24
0 to 10
0.024
0.12 amps
40
.27
0 to 10
0.027
0.135 amps
50
.48
0 to 10
0.048
0.24 amps
60
.48
0 to 10
0.048
0.24 amps
This RATIO takes effect when the Mode 1 settings are
called for by the Interactive Dash Display.
FUNCTION 52
MODE 2 ARMATURE CONTROLLED
ACCELERATION AND 1A TIME
(Push
CONT
5)
Same as Function 48.
This C/A AND 1A TIME takes effect when the Mode 2
settings are called for by the Interactive Dash Display.
FUNCTION 53
MODE 2 FIELD WEAKENING START
(Push
CONT
6)
Same as Function 49.
This FIELD WEAKENING START takes effect when the
Mode 2 settings are called for by the Interactive Dash
Display.
FUNCTION 54
MODE 2 MINIMUM FIELD CURRENT
(Push
CONT
7)
Same as Function 50.
This MINIMUM FIELD CURRENT takes effect when the
Mode 2 settings are called for by the Interactive Dash
Display.
FUNCTION 55
MODE 2 RATIO
(Push
CONT
8)
Same as Function 51.
This RATIO takes effect when the Mode 2 settings are
called for by the Interactive Dash Display.
FUNCTION 56
MODE 3 ARMATURE CONTROLLED
ACCELERATION AND 1A TIME
(Push CONT 9)
Same as Function 48.
This C/A AND 1A TIME takes effect when the Mode 3
settings are called for by the Interactive Dash Display.
FUNCTION 57
MODE 3 FIELD WEAKENING START
(Push
CONT
10)
Same as Function 49.
This FIELD WEAKENING START takes effect when the
Mode 3 settings are called for by the Interactive Dash
Display.
FUNCTION 58
MODE 3 MINIMUM FIELD CURRENT
(Push
CONT
11)
Same as Function 50.
This MINIMUM FIELD CURRENT takes effect when the
Mode 3 settings are called for by the Interactive Dash
Display.
FUNCTION 59
MODE 3 RATIO
(Push
CONT
12)
Same as Function 51.
This RATIO takes effect when the Mode 3 settings are
called for by the Interactive Dash Display.
FUNCTION 60
MODE 4 ARMATURE CONTROLLED
ACCELERATION AND 1A TIME
(Push
CONT
13)
Same as Function 48.
This C/A AND 1A TIME takes effect when the Mode 4
settings are called for by the Interactive Dash Display.
FUNCTION 61
MODE 4 FIELD WEAKENING START
(Push
CONT
14)
Same as Function 49.
This FIELD WEAKENING START takes effect when the
Mode 4 settings are called for by the Interactive Dash
Display.
FUNCTION 62
MODE 4 MINIMUM FIELD CURRENT
(Push
CONT
15)
Same as Function 50.