background image

GEK-86105 

position.  The  core 

has 

been  factory  set  to  obtain 

80% 

dropout  at  the  m1n1mum 

setting,  and  a

pp

r

o

x

i

m

ate

l

y  90% 

dropout  at  the  maximum  setting.  To  change  the 

d

ro

p

o

u

setting,  the 

sleeve 

(C) 

to 

which  the  shading  ring 

(

D

is  a

tt

a

c

h

ed 

must 

always  be  turned  in  the  clockwise  direction  (top 

view). 

This 

wil l 

prevent 

the 

sleeve  and 

s

h

a

d

i

n

ring  assembly  from  being 

loosened. 

When  s

hi

pp

e

from  the 

factory,  the whole coil is wired  into the current circuit, 

and  t

h

lower half of the 

cal

ib

r

a

t

i

on 

range  is  available. 

If 

the 

up

pe

r  half 

of 

t

h

calibr·ation  range 

is 

required,  the  tapped 

s

e

c

t

i

on  of the  coil should 

be 

wi

r

e

d  into the  current circuit. 

Do thi

by 

ta

king 

the 

black lead off stud 6 and 

the 

green lead  off stud 6A.  Then 

put 

the  gren  lead  on 

stud 6 

and 

t

h

e black lead on stud 6A 

(see 

Figure 

9). 

The  unit  will  pick  up  at  the  scale  pl

at

m

ark

i

n

..:!: 

5% 

with  gradually  applied 

current.  Figure 10 shows the transient overreach characteristics.  Burden data for 

the 

60 hertz high dropout unit is tabulated in 

Table 

IX. 

RANGE 

AMPERES 

4  - 16 

- 28 

10  - 40 

20  - 80 

TABLE IX 

BURDEN OF 60 HERTZ HIGH DROPOUT INSTANTANEOUS UNIT 

BURDEN AT MINIMUM PICKUP 

SETTING AND MINIMUM CURRENT 

R OHMS  X OHMS  Z OHMS 

3.16 

0.79 

0.2 

0.07 

0.03 

0.007 

3.16 

0.79 

0.2 

0.07 

0.03 

0.007 

4.48 

1.12 

0.28 

0.1 

0.04 

0.01 

VOLT-AMPERES AT FIVE AMPERES 

CALCULATED FROM INPUT AT 

MINIMUM PICKUP  I2Z 

112.0 

28.0 

7.0 

2.50 

1.00 

0.25 

CONSTRUCTION 

The IAC66M 

r elay 

is 

mounted in an Ml case that does not 

h ave 

an upper contact block. 

The case 

is 

su

i

t

a

b

l

for either semi-flush or surface mounting  on panels up to two 

inches 

thick. 

Hardware  is 

available 

for 

al1  panel thicknesses.  To be sure that the 

proper  hardware  will  be  provided,  panel  thickness should  be specified  on 

the 

or

de

for the relay.  Outline and panel drilling dimensions are shown in Figure 3. 

The  relay  components  are  mounted 

on  a 

cradle 

assembly  that  can 

e

a

s

il

be 

removed 

frorr the  relay case. 

The  cradle  is 

locked  in 

the  case  by 

l

a

t

c

h

e

at 

the  top  and 

bottom. 

Electrical 

connections 

between 

case 

and cradle 

blocks 

are c

o

mp

l

et

e

th

ro

u

gh 

removable 

connection 

p

l

u

g

s

Separate 

testing 

plugs 

can 

be 

inserted 

in 

place 

of 

the 

connectior 

plugs  to 

test 

the 

relay 

in  i

t

case.  The cover 

is  attached  to 

the 

case 

from  the  front, 

and 

includes  an  interlock 

arm  that 

p

rev

ent

the  cover 

from 

being 

replaced 

until 

the connection plug 

has 

been inserted. 

The 

induction 

unit,  consisting  of 

U-magnet,  drag 

m

a

g

n

e

and 

a  disk 

assembly,  is 

m

o

unt

ed 

on  a 

m

eta

l  frame. 

The  pickup  of  the  induction  unit  is 

set 

by  a 

ta

block 

located  near  the  middle 

of 

t

h

relay. 

The  time  delay  is  adjusted  by 

turning  the 

molded 

time 

dial,  located just below the ta

b

l

o

c

k

The 

standard 

instantaneous 

unit is 

m

o

u

n

ted  just 

above 

the  drag  magnet 

on  the  right 

hand 

s

i d

e

The  adjustable  core  can  be 

r

a

i

s

e

or 

l

o

w

e

r

ed 

to  change  the  pickup 

of the 

u

n

i

t. 

www 

. ElectricalPartManuals 

. com 

Содержание IAC66M

Страница 1: ...INSTRUCTIONS TYPE IAC66M TIME OVERCURRENT RELAY GENERAL f ELECTRIC Gt K 86105 Supersedes CE 1 6b75 I h w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...DENS 6 INDUCTION UNIT 6 TARGET AND SEAL IN UNIT 6 TELEPHONE RELAY 7 STANDARD INSTANTANEOUS UNIT 7 HIGH DROPOUT INSTANTANEOUS UNIT 8 CONSTRUCTION 9 RECEIVING HANDliNG AND STORAGE 10 ACCEPTANCE TESTS 10 VISUAL INSPECTION 1 0 MECHANICAL INSPECTION 11 ELECTRICAL TESTS 11 INSTALLATION 13 PERIODIC CHECKS AND ROUTINE MAINTENANCE 14 SERVICING 14 RENEWAl PARTS 14 2 w w w E l e c t r i c a l P a r t M a n u...

Страница 3: ...RATINGS INDUCTION UNIT The induction unit coil is available in several ranges of pickup current Table I lists ranges tap values continuous current ratings and short time current ratings of the induction unit coil The induction unit contacts will close 30 amperes for voltages not exceeding 250 volts The current carrying ratings are affected by the tap selected on the target and seal in coil as indi...

Страница 4: ...belled on the tap block To obtain a tap value of 4 0 amps on the 2 5 7 5 amp relay use taps D H TA BLE II RATINGS OF TA RGET AND SEAL IN CO ILS CURRENT OP ERA T E D Carry 30 amps for Carry 10 amps for Carry continuously Minimum operating Minimum dropout DC res istance 60 hertz impedance 50 hertz impedance SIX CYCLE TIME D ELAY TELEPHONE RE LAY seconds seconds amperes amperes amperes ohms ohms ohms...

Страница 5: ... 40 15 0 205 20 80 30 0 326 40 160 60 0 326 For forms 51 and up the standard instantaneous unit has the foll owing ratings l isted in Table IVb TABLE IVb STANDARD INSTANTANEOUS UNIT COIL RATINGS FORMS 51 AND UP SERIES OR RANGE PARALLEL 0 5 4 0 0 5 2 0 Series 1 0 4 00 Para11 e 1 2 0 16 0 2 0 8 0 Serie s 4 0 16 0 Parallel 10 0 80 0 10 0 40 0 Series 20 0 80 0 Paral l el 20 0 160 0 20 0 80 0 Series 40...

Страница 6: ...es electrical contact with a fixed member Figure 6 gives the time for the induction unit to close its contacts for various multiples of pickup current and time dial settings The time required for this unit to reset from contact closure to the Number 10 time dial position is approximately 60 seconds Burden data for induction unit coils is listed in Table VIa The impedance values are for the minimum...

Страница 7: ... 4 48 4 0 4 05 SIX CYCLE TIME DELAY TELEPHONE RELAY 15 2 0 13 12 7 0 13 6 7 0 13 5 6 0 13 2 5 0 13 2 1 0 13 0 95 0 13 0 79 0 13 as shown in Table 51 AND UP IMP POWER OHMS FACTOR 4 43 0 32 1 92 0 33 0 71 0 35 0 46 0 37 0 27 0 44 0 23 0 47 0 18 0 52 0 16 0 47 Vlb As mentioned the telephone relay OX has a six cycle time delay after it is energized through the high dropout instantaneous contacts The o...

Страница 8: ... 04 0 71 20 80 50 5 0 23 0 01 0 77 60 5 0 25 0 01 o 71 40 160 50 5 0 07 0 003 0 71 60 5 0 07 0 003 0 71 Volt amperes at five amps calculated from input at minimum pickup 12z HIGH DROPOUT INSTANTANEOUS UNIT The high dropout instantaneous unit is similar to the standard instantaneous unit except the dropout current is approximatel y 80 to 90 of the pickup current Refer to Figure 8 a photograph of th...

Страница 9: ...ICKUP I2Z 112 0 28 0 7 0 2 50 1 00 0 25 CONSTRUCTION The IAC66M r elay is mounted in an Ml case that does not have an upper contact block The case is suitable for either semi flush or surface mounting on panels up to two inches thick Hardware is available for al1 panel thicknesses To be sure that the proper hardware will be provided panel thickness should be specified on the order for the relay Ou...

Страница 10: ...is evident file a damage claim at once with the transportation company and promptly notify the nearest General Electric Sales Office If the equipment is not to be installed immediately it should be stored indoors in its original carton in a location that is dry and protected from dust metallic chips and severe atmospheric contaminants ACCEPTANCE TESTS An inspection and acceptance test should be ma...

Страница 11: ...to be made with the relay in its case and in a level position All alternating current operated devices are affected by frequency sinusoidal waveforms can be analyzed as a fundamental frequency plus the fundamental frequency it follows that alternating current devices be affected by the applied waveform Sinee non harmonics of relays will Therefore in order to properly test alternating current relay...

Страница 12: ...elay should pick up at 80 or less of its rating 4 Apply rated voltage to the OX unit The contacts should close six cycles 0 1 second after voltage is applied Target Seal in Units There are two target seal in units associated with the IAC 66M A relay The target seal in in the lower l eft front view is in the induction unit standard instantaneous unit circuit The other target seal in is located in t...

Страница 13: ...STALLATION MOUNTING AND CONNECTIONS Outline and panel drilling dimensions are shown in Figure 3 Unless the relay is mounted on a steel panel which adequately grounds the relay case the case should be grounded through a mounting stud or screw with a conductor not less than No 12 B S gage copper wire or equivalent Internal connections are shown in Figure 9A Figure 9B shows the internal connections f...

Страница 14: ... brings the operating current of the unit into agreement with the tap setting This adjustment al so makes any setting between the various tap settings possibl e Note however that if pickup is changed by turning the spring adjusting ring then the rel ay wil l be operating at a different torque level and the published time curves wil l not apply for this setting The unit has been factory adjusted to...

Страница 15: ...otograph IAC66M Relay Construction Relay Removed from Drawout Case Front View Figure 2 8027185 Photograph IAC66M Relay Construction Relay Removed from Drawout Case Rear View 15 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 16: ...BERING OF STUDS B CK VIEW 15MM DRILL 4 HOLES 7 40 I IBOMM II I 6UU ORILL _ I 250 6 HOLES PANEL D RLUN6 FOR SEMI FLUSH MOUNTING FRONT VIEW VIEW IHOWINb GMM A SEMSLY Of HARD 133M M WARE SURFA CE 5 25 MT i ON STEEL PANELS PANEL DRILLING FOR SURFACE MOUNTING FRONT V lEW Figure 3 6209273 3 Outl ine and Panel Drilling Dimensions for the IAC66M Relay 16 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Страница 17: ...ERMINAL BLOCK Figure 4 8025039 Photograph Cross Section of Drawout Case Showing Position o f Auxiliary Brushes 51 1 SI OC BU S T 51 52 s1 1 so 1 so f TOC Icc A IOC 3 SO roc A 51 sr 8 1 I 1 2 1 3 6 so IOC 13 ONE PHPSE ONLY IS S tO WN 5 0 6N PI ox I Figure 5 0207A7826 0 External Connections Diagram for IAC66M Relay 17 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ..._ 1 r _ 4 t I 1 I 111 GEK 86105 JO 40 5I 10 lO 10 1 g 8 7 f 6 5 1 4 3 en 2 0 E P t 1 I lO 44 I 10 70 10 I II MULTIPLES OF RELAY TAP SETTING I i I i 1111I 1 I I I I I 1 M I I I UU Figure 6 0888B0273 0 Time Current Characteristics of IAC66M Rel ay 18 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...ME RANGE FOR ANY v PICKUP SETIINCi t I _ I I 3 5 6 7 8 Figure 7 0208A8695 l Operating Time Versus Current for the Standard Instantaneous Unit ADJUSTAI E CQf rA lOCKNUT SlEEVE C _ I 9 Figure 8 8036365 Photograph High Dropout Unit Construction 19 ___ 10 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 20: ...or the IAC66M Relay Front View 1i n 4 0 t t N f r OWN 1 f E LONN B AN ILJ10H M Q IN AN A l l T f M L l lll lo v NH C0NN A 5 S C wN H RANGE REV r E t REEN i 1 6LACK lEADS N TtRM 6 A NO 6 A SHORT FINGER OX AUX lt L H0 E REL AV Figure 98 0285A8839 0 Internal Connections Diagram for the IAC66M Relay Forms 51 and Up Front View 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ... rt lll ro N s s g n s o VI c m rtQj n r 0 rt r t 0 r 0 0 0 0 s rt 1 t ill 4 Hf 10 5 I TRANSIENT OVERREACH HNC RELAY lliilmmmammtm111111 m mrmiIt tmtilli it HIll 111 11111111 H en I co O t Q TI w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 22: ...l 3 s ffiT FINGER i 6 NST HI DROP OUT Wf1JERJ OX AU TELEftlCNE RELAY ox I j HI DROP OUT UPPER ox r 9 10 Sl UPPER WHEN USED FOR 250 V D C Figure 11 0104A8596 2 Internal Connections Diagram for the Timer Unit IAC66M Relay Forms 1 50 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ...N AS HOWN HI RANGE CONN BAND D TOTERM 7 CONN C AND A TO TERM 4 HI G INST UNIT LOW RAN GE CONN AS SHOWN HI RANGE REVERSE GR EN AND BLACK LEADS ON T RM 6 AND 6 A 7 P S R R7 9 8 tO SHORT FINGER OX AUX TELEPHONE RELAY Figure 12 0285A8839 Internal Connections Diagram for the Timer Unit IAC66M Relay Forms 51 and Up 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 24: ...GE Power Management 215 Anderson Avenue Markham Ontario canada L6E 183 Tel 905 294 6222 Fax 905 201 2098 www ge com indsys pm w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: