F. WINTERIZATION PROCEDURE

Tools/Supplies Required

For all Systems you will need:
• 

Cap Wrench

• 

Adjustable wrench

• 

Nut driver

• 

3 US gallons (12 litres) plumbers antifreeze that is 

propylene glycol based and rated for -58°F (-50°C).

• 

1 - ¾” MNPT PVC plug

• 

1 - ½” MNPT PVC plug

  

WARNING: 

Never use AUTOMOTIVE 

type antifreezes when winterizing the System. This may 

result in serious injury or death.
Only plumbing antifreeze, consisting primarily of 

propylene glycol with no ethanol or other alcohols, 

rated for -58°F (-50°C), may be used to winterize the 

System. The use of less-expensive 

 

‘non-propylene glycol based’ plumbing or RV 

antifreezes may damage the System’s internal 

components voiding all warranties. This may also 

 

result in serious injury or death.
Plumbing antifreeze containing propylene glycol will 

provide protection of the System against freezing to 

-40°F (-40°C) as long as the proportion of antifreeze 

to water is correct. This procedure only protects the 

System from freezing and does not protect the rest of 

the household water distribution system.
Propylene glycol based antifreeze is available at most 

hardware stores.

Close the Inlet Valve. Completely drain the System and 

household piping. To drain the System, refer to the Controller 

Functions section under D. OPERATIONS on how to perform a 

Manual Flush. To drain the household pipes, open a cold water 

tap (on the lowest level of the home) and leave until the tap 

only drips. Turn off the tap when the pipes are drained.

FIGURE 9

All valves closed

Remove the drain hose and Nylon Elbow from the Drain 

Solenoid Valve and install a ½” MNPT or ¾” MNPT PVC plug 

(depending on the size of the port) into the Drain Solenoid 

Valve. 

3

Drain the filtered water from the System by 

disconnecting the Outlet Stainless Steel Flex Hose where it 

connects to the home plumbing, and drain into a large bucket. 

Plug the Flex Hose and System by installing a ¾” MNPT PVC 

plug.

Disconnect and 

Plug here

Outlet Fitting Assembly installed in standard configuration 

shown. Systems equipped with the Surface Water Option Kit 

have different Outlet Fitting Assemblies.

FIGURE 10

4

If an External Prefilter has been installed, open the Mini 

Ball Valve on the bottom of the housing and allow to drain. 

Press the red button on the External Prefilter head to speed up 

draining. Unscrew the housing from the head and remove the 

External Prefilter cartridge from the housing, and discard. Do 

not install a new filter cartridge. Re-attach the filter housing to 

the head.

FIGURE 11

Содержание Homespring

Страница 1: ...1 HomespringTM by GE Water Purifier System Owners Manual...

Страница 2: ...CTION 3 B SAFETY WARNINGS 4 5 C CERTIFICATION 5 D OPERATIONS 6 8 E MAINTENANCE SCHEDULE 9 11 F WINTERIZATION 12 15 G TROUBLESHOOTING 15 16 H REPLACEMENT PART LIST AND PROCEDURES 17 21 I SPECIFICATIONS...

Страница 3: ...asic principles of household water collection treatment and discharge and some of the features of the Homespring Water Purifier System It is not intended to be a definitive dissertation on the princip...

Страница 4: ...rvice provided it is installed commissioned operated maintained and tested in strict accordance to the safety instructions contained in this manual Failure to properly maintain the System will comprom...

Страница 5: ...lar to the water pipe 2 Open Inlet and Outlet Valves If ball valves are installed turn the handles in line with the water pipe 3 Plug in the Controller 4 Follow the System Membrane Cleaning section un...

Страница 6: ...cial attention under normal operating conditions The System uses existing water pressure in the water supply line to filter water and will continue to operate even during a power failure Electricity i...

Страница 7: ...Kit is installed select either Program 3 or Program 4 in this application Water Clarity Advanced Plus Controller Low Turbidity Less than 0 5 NTU Program 1 Medium Turbidity Peaks to 1 0 NTU less than 7...

Страница 8: ...utton is held down for 5 seconds the Drain Solenoid Valve will remain open for 5 minutes To interrupt flushing press MANUAL FLUSH again The Drain Solenoid Valve will be closed automatically after 5 mi...

Страница 9: ...be performed every 12 months unless specified otherwise Refer to H REPLACEMENT PART LIST AND PROCEDURES for part numbers System Part Annual Maintenance Tasks UFC 211 UF 211 Carbon Prefilter Replace W...

Страница 10: ...tire procedure to avoid contaminated water entering the household distribution system Contaminated water might cause personal injury and in some cases death This cleaning procedure does NOT disinfect...

Страница 11: ...ath Replace the System Cap Vertical Systems or the Brass Plug Horizontally mounted Systems Let stand for 60 minutes Annual Maintenance Check Summary The Homespring Authorized Technician performs the f...

Страница 12: ...etely drain the System and household piping To drain the System refer to the Controller Functions section under D OPERATIONS on how to perform a Manual Flush To drain the household pipes open a cold w...

Страница 13: ...vity FIGURE 13 7 If a Stainless Steel Prefilter has been set aside place the Stainless Steel Prefilter in the Prefilter cavity 8 For all Sytems replace the System Cap using the Cap Wrench and check bo...

Страница 14: ...ssary Add 2 cups 500 ml of unscented household bleach 5 6 chlorine or 1 cup 250 ml chlorine bleach 12 chlorine maximum 3 months old to the System 8 Allow the System to soak for 15 minutes With the Sys...

Страница 15: ...ace is clean and is intact Ensure connections are tight Contact your Dealer System water flow is noticeably reduced Check if Thimble Filter is clogged Depressurize System remove System Cap and Interna...

Страница 16: ...unctions section under D OPERATIONS on how to perform a manual flush sequence and ensure button on controller is pressed for a full 5 seconds A buzz sound should be heard from the Drain Solenoid Valve...

Страница 17: ...remove the System Cap 4 Put on a pair of disposable gloves and carefully remove and dispose of the Internal Prefilter Check that the Thimble Filter is in place seated in the spigot DO NOT attempt to...

Страница 18: ...18 UFC 211 and UF 211 Series FIGURE 20 24 13 6 10 3 5 11 1 2 17 18 20 19 21 16 4 3 7 8 22 23 14 15 12 9...

Страница 19: ...3024987 Cap Wrench UF 211 X 14 Backpulse Tank X 15 3035560 Controller Power Supply DC X Sub Assembly Kits 16 3025172 Installation Sub Assembly Kit Base shims anchors Mini Ball Valves with Plugs 2 Nylo...

Страница 20: ...4 FNPT Flapper X 6 3025096 Brass Nipple 3 4 X 7 3030405 External Prefilter Housing and Head X 8 3025174 Wall Bracket Kit Filter Housing X 9 3025371 Mini Ball Valve Plug 1 4 X 10 3024982 Mini Ball Val...

Страница 21: ...aims are based on a continuous flow of 4 5 gpm 17 Lpm 2 Pressure drops are given for systems when they are new and equipped as specified by the model number At temperatures below 77 F 25 C the pressur...

Страница 22: ...nside the dwelling will be significantly reduced during System cleaning Flushing Flushing includes a Front flush and a Back flush Systems that are installed in municipal cistern or ground water source...

Страница 23: ...een a water quality issue such as a recent boil water alert or water main break from the municipal water source the household pipes should be sanitized upon installation of the System How long does th...

Страница 24: ...ling the System excluding the attached parts will need to be replaced Will the System remove iron sulfur The pore size of the membrane is 0 02 microns nominal which may help in the filtration of parti...

Отзывы: