NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
14
Power Input Panel
Power Input
Terminal blocks in a front
access panel at the bottom
of the distribution box.
Figure 7 Power Input Panel
Battery Options and Monitoring Features
Figure 8 Battery Stand
Battery
Options
•
Designed for operation with GE flooded, VRLA and Durathon™ Sodium batteries, as
well as other vendors’ batteries.
•
Battery trays are available for 100Ahr to 170Ahr batteries with Anderson
PowerPole® connectors or circuit breaker disconnects.
•
Half-height and third-height systems can be mounted on floor-mounted VRLA
strings or on GE Universal Battery Stands.
Battery Monitoring Features
•
Open String (OS) Alarms
•
Emergency Power Off (EPO) for disconnecting batteries from the system
•
Temperature/voltage probes (up to 16) used in Battery Management options
•
Slope Thermal Compensation – High and Low Temperature
•
Battery High Temp Disconnect
•
Mid-String Voltage Monitoring
•
Battery Discharge Test
•
Battery Shunt
•
Low Voltage Battery Disconnect/Reconnect Contactor (LVDB)
with Emergency Power Off (EPO)
Knockouts
each side:
(2) 1” and
(2) 1-1/2”
Terminal Blocks Accept 24-
6 AWG wire.
Straps provided to
feed rectifier pairs.
Conduit Ground
¼-20 x 0.75” or
0.625” Studs