When neutral wire of inverter is not connected to grid, "Delta Grid" should be selected in grid 
type(IT) setting page.

IT

L1

L2

L3

Transformer

PE

 

Inverter

3.2 Inverter Overview

3.2.1 GEP series inverter illustration

3.2.2 DC Switch

The DC switch is designed such that the DC input can be disconnected safely.

The inverter works automatically when the input and output meet the requirements. Rotating the 
DC switch to "OFF" position will immediately cut off the flow of DC current.Rotate the DC switch to 
"ON" position before starting the inverter.

3.3 Technical Description

3.3.1 Principle Description

PV string voltage is transmitted to DC BUS via BOOST circuit.

The GEP series is equipped with Three or Six MPPTs for Six, Tweleve DC inputs to ensure that 
the maximum power is utilized even in different PV installation condition.

DC/AC converter circuit convert DC power into AC power, which can be fed into the utility. 
Protective circuit are designed to protect the inverter safety and human safety.

DC switch is integrated to allow for a safe disconnection from the DC input. The inverter provides 
standard interface RS485, WIFI for communication. Inverters also provide running recode data 
display, parameter configuration via LCD panel.For the main block diagram please refer to chapter 
7.2.

3.3.2 Function Description

Inverter functions can be grouped as following.

1. Conversion function

Inverter converts direct current power into alternating current power, which conforms to the grid 
requirement of its installation country.

Image shown here is for reference only, actual product you receive may differ.

 

Item

1

2

3

4

5

6

7

8

9

Name

 

DC Switch

PV Input Port

WiFi

RS485&DRED&USB&Remote Shutdown

 Communication Port

AC output port

LED indicator light

LCD display screen

Buttons

Air Outlet

Description

During normal operation it is in "on" state, it can shut down
the inverter after it is disconnected from the grid by the AC breaker.

For PV string connection

WiFi For connection

For RS485 And DRED And USB And Remote Shutdown 

Communication

For AC cable connection

Display the state of the inverter

Inverter operation data viewing and parameter configuration.

For configuration and viewing parameters.

Exit of hot air during the inverter operation.

GEP12~20-L-10

GEP25~36-10

WITH LCD

 

WITHOUT LCD

6

7

9

8

1

2

4

5

3

GEP30~35-L-10

GEP50~60-10

WITH LCD

WITHOUT LCD

6

7
8

9

1

2

3 4

5

Содержание GEP12-L-10

Страница 1: ...UAL Global Sales Service Network GE is a registered trademark of General Electric Company and is used under license by GoodWe Technologies Co Ltd No 90 Zijin Rd New District Suzhou 215011 China www ge...

Страница 2: ...7 5 System Operation 21 5 1 LCD Panel And LED 21 5 2 User Interface Introduction 22 5 3 System Configuration 25 5 4 Precaution For Initial Startup 30 5 5 Setting Inverter Parameters via App 31 5 6 Mon...

Страница 3: ...work All detailed work related safety warnings and notes will be specified at the critical points in corresponding chapter All installation and electrical work must only be performed by qualified per...

Страница 4: ...ons which will lead to potential injury to people and damage to inverters Static electricity may damage electronic components Appropriate method must be adopted to prevent such damage to the inverter...

Страница 5: ...ter provides standard interface RS485 WIFI for communication Inverters also provide running recode data display parameter configuration via LCD panel For the main block diagram please refer to chapter...

Страница 6: ...ommunication Terminal Grounding Screw Expansion Bolt Safe Screw Connecting Terminal Grounding AC Cover OT Terminal Insulation Sleeve WiFi Module WiFi communication Or without LCD Quick Installation In...

Страница 7: ...values The Upward part The downward part The front part Both sides Interval 200mm 500mm 500mm 600mm 1200mm 500mm 1200mm 600mm 600mm 500mm 300mm The Upward part The downward part The front part Both si...

Страница 8: ...low these steps to connect the utility and inverter 7 If the diameter of the cable does not match the terminal or if the cable is aluminum cable please contact after sales service Two mounting holes i...

Страница 9: ...et of a suitable length with a wire stripper Output Current 31 5A 40A 54 5A 40A 43 3A 48A 53 3A 80A 96A 80A 96A Inverter Model GEP12 L 10 GEP15 L 10 GEP20 L 10 GEP25 10 GEP29 9 10 GEP30 10 GEP36 10 GE...

Страница 10: ...not met The GEP series has three PV input area PV1 input PV2 input PV3 input each with MPPT tracker therefore the three PV input can be different with each other including different type of modules di...

Страница 11: ...zlogger Pro manual Remote shutdown is only for European installations in compliance with European safety requirements A remote shutdown device is not provided by manufacturer DRED should be connected...

Страница 12: ...ion This function is only applicable for WiFi model for specific configurations please refer to WiFi LAN Configuration Instruction in the attachment and you can also refer to the description of Demo V...

Страница 13: ...ive On Fault occurred OFF No fault Status Indicator Green green green red light respectively corresponds to 5 2 User Interface Introduction Communication information icon GPRS and WiFi show the signal...

Страница 14: ...Fi 22 93 3kWH 4 E TOTAL E DAY 01 01 2020 00 00 00 CARBON Fault Utility Loss 0 0kWH Basic Advanced WiFi 22 105 3kWH 4 E TOTAL E DAY 01 01 2020 00 00 00 Fault WiFi Con guration 22 Basic Advanced 01 01 2...

Страница 15: ...0 00 Fault Country Code Holland Northlreland ChinaHigher France 50Hz France 60Hz WiFi 22 01 01 2020 00 00 00 Fault Language WiFi 22 01 01 2020 00 00 00 Fault Data Time WiFi 22 01 01 2020 00 00 00 Faul...

Страница 16: ...i 22 01 01 2020 00 00 00 Normal Adv Settings HVRT Grid Type Password Factory Data Reset WiFi 22 01 01 2020 00 00 00 Normal Adv Settings HVRT Grid Type Password Factory Data Reset WiFi 22 01 01 2020 00...

Страница 17: ...0 6 0 4 0 2 0 4 6 8 10 12 14 16 18 20 Month Year Basic Advanced 01 01 2020 00 00 00 Fault WiFi Con guration 22 Basic Advanced 01 01 2020 00 00 00 Normal WiFi Con guration 22 01 01 2020 00 00 00 Norma...

Страница 18: ...local service office 1 Disconnect the DC switch take off DC connector check PV string voltage check if it exceeds the input voltage in inverter specification 2 If it does please reconfigurate PV panel...

Страница 19: ...ber of MPP Trackers Number of Strings per MPPT Output AC Nominal Output Power W Nominal Output Apparent Power VA Max AC Active Power W Max AC Apparent Power VA Nominal Power at 40 W Max Power at 40 In...

Страница 20: ...rent A Max Output Fault Current Peak and Duration A ms Inrush Current Peak and Duration A us Nominal Output Current A Power Factor Max Total Harmonic Distortion Efficiency Max Efficiency Europen Effic...

Страница 21: ...T Output AC Nominal Output Power W Nominal Output Apparent Power VA Max AC Active Power W Max AC Apparent Power VA Nominal Power at 40 W Max Power at 40 Including AC Overload W Nominal Output Voltage...

Страница 22: ...pment in an industrial installation Category IV applies to equipment permanently connected at the origin of an installation upstream of the main distribution board For example electricity meters prima...

Страница 23: ...PV plant Caution Before maintenance please disconnect the AC breaker rst and then disconnect DC breaker Wait 5 minutes until the residual voltage has been released 8 1 Clearing The Fan Series inverte...

Отзывы: