37
38
*1
:
For Brazil Max. Output Power GEP50-10 is 50000W, GEP60-10 is 60000W.
*2
:
For Brazil Max. Output Apparent Power GEP50-10 is 50000W, GEP60-10 is 60000W.
*3
:
For Brazil Nominal Output Voltage GEP50-10 is 380V, GEP60-10 is 380V.
*4
:
For Brazil Communication GEP50-10 is RS485, WiFi, USB, PLC (Optional); GEP60-10 is RS485,WiFi,USB,PLC (Optional).
Moisture parameters
Temperature Range
Humidity Range
3K3
0~+40℃
5%~85%
4K2
-33~+40℃
15%~100%
4K4H
-20~+55℃
4%~100%
Level
Note:
Overvoltage Category Definition
Category I: applies to equipment connected to a circuit where measures have been taken to
reduce transient overvoltage to a low level.
Category II: applies to equipment not permanently connected to the installation. For example,
appliances, portable tools and other plug-connected equipment;
Category III: applies to fixed downstream equipment, including the main distribution board. For
example,switchgear and other equipment in an industrial installation;
Category IV: applies to equipment permanently connected at the origin of an installation
(upstream of the main distribution board).For example, electricity meters, primary
overcurrent protection equipment and other equipment connected directly to
outdoor open lines.
Moisture Location Category Definition
Environment Category Definition
Outdoor : the ambient air temperature is -20~50℃. Relative humidity range is from 4% to 100%,
applied to PD3.
Indoor unconditioned: the ambient air temperature is -20~50 ℃. Relative humidity range is from
5% to 95%, applied to PD3.
Indoor conditioned: the ambient air temperature is 0~40 ℃. Relative humidity range is from 5% to
85%, applied to PD2.
Pollution Degree Definition
Pollution degree 1: No pollution or only dry, non-conductive pollution occurs. The pollution has
no influence.
Pollution degree 2: Normally only non-conductive pollution occurs. However, a temporary
conductivity occasionally caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs. Or dry, non-conductive pollution becomes
conductive due to condensation, which is expected.
Pollution degree 4: Persistent conductive pollution occurs. For example, the pollution cause by
conductive dust, rain and snow.
Integrated
Integrated
Integrated
Optional
Type II(Type I optional)
Type II
Integrated
Integrated
Integrated
Integrated
Class I
C
-30~60
0~100%
≤3000
Fan Cooling
LCD & LED or APP & LED
55
520*660*220
IP65
<1
Transformerless
IEC62109-1&2
EN61000-6-1,EN61000-6-2,EN61000-6-3,EN61000-6-4
Technical Data
PV String Input Data
Max. DC Input Power (W)
Max. DC Input Voltage (V)
MPPT Range (V)
Start-up Voltage (V)
Nominal DC Input Voltage (V)
PV Input Operating Voltage range
(
V
)
Max. Inverter Backfeed Current To The array (A)
Max. Input Current (A)
Max. Short Current (A)
No. of MPP Trackers
No. of Input Strings per Tracker
AC Output Data
Nominal Output Power (W)
Max. Output Power (W)
Max. Output Apparent Power (VA) [1]
Nominal Output Voltage (V)
Nominal Output Frequency (Hz)
Max. Output Current (A)
Output Power Factor
Output THDi (@Nominal Output)
Current
(
inrush
)
Maximum Output Fault Current
Maximum Output Over Current Protection (A)
Efficiency
Max. Efficiency
Europen Efficiency
Protection
Anti-islanding Protection
Input Reverse Polarity Protection
PV String Current Monitoring
Anti-PID Function for Module
DC Surge Protection
AC Surge Protection
Residual Current Monitoring Unit
Output Over Current Protection
Output Short Protection
Output Over Voltage Protection
Protective Class
Decisive Voltage Classification
(
DVC)
General Data
Operating Temperature Range (
℃
)
Relative Humidity
Operating Altitude (m
)
Cooling
User Interface
Communication
Weight (kg)
Size (Width*Height*Depth mm
)
Protection Degree
Night Self Consumption (W)
Topology
Certifications & Standards
Grid Regulation
Safety Regulation
EMC
~1 (Adjustable from 0.8 leading to 0.8 lagging)
GEP30-L-10
39000
800
200~650
180
370
180~800
0
26/26/26/26/26
33/33/33/33/33
5
2/2/2/2/2
30000
30000
30000
220, 3L/N/PE or 3L/PE
50/60
80
<3%
50
300
195
98%
97.7%
GEP50-10
75000
1100
200~950
180
600
180~1100
0
26/26/26/26/26
33/33/33/33/33
5
2/2/2/2/2
50000
55000
*1
55000
*2
400
*3
, 3L/N/PE or 3L/PE
50/60
80
<3%
50
300
195
98.3%
98%
GEP35-L-10
45500
800
200~650
180
370
180~800
0
26/26/26/26/26/26
33/33/33/33/33/33
6
2/2/2/2/2/2
35000
35000
35000
220, 3L/N/PE or 3L/PE
50/60
96
<3%
50
300
195
98%
97.7%
GEP60-10
90000
1100
200~950
180
600
180~1100
0
26/26/26/26/26/26
33/33/33/33/33/33
6
2/2/2/2/2/2
60000
66000
*1
66000
*2
400
*3
, 3L/N/PE or 3L/PE
50/60
96
<3%
50
300
195
98.3%
98%
RS485
,
WiFi
,
USB
,
PLC
(
Optional
)
IEC61727
,
IEC62116
RS485
,
WiFi
*4
,
PLC
(
Optional
)
IEC61727
,
IEC62116
,
AS4777.2
Содержание GEP
Страница 24: ......