5.3.3 History Information
The history information mainly includes the information of the generating capacity of the equip-
ment, the power generation information mainly includes the amount of electricity generation, daily
power generation, monthly power generation and annual power generation information.
5.4 Precaution For Initial Startup
1. Make sure the AC circuit is connected and AC breaker is turned off.
2. Make sure the DC cable between inverter and PV string is connected, and the PV voltage is
normal.
3. Turn on the DC switch, and set safety according to the local regulation.
4. Turn on the AC breaker, and check the inverter work normal.
5.3.4 Wi-Fi Reset & Wi-Fi Reload
WiFi
22
01/01/2020 00:00:00
Fault
Configuration
Language
Data&Time
Communication
Country Code
Grid Connection
WiFi Reload
WiFi Reset
01/01/2020 00:00:00
Fault
WiFi
WiFi Set
22
WiFi
22
01/01/2020 00:00:00
Fault
Communication
Modbud Address
WiFi Set
01/01/2020 00:00:00
Fault
WiFi
History Info
22
Hour
Day
2020-01-01
36kWh
1.0
0.8
0.6
0.4
0.2
0
4
6
8
10
12
14
16
18
20
Month
Year
5.5 Special Adjustable Setpoints
The inverter has a field in which the user can set functions, such as trip points, trip times, recon-
nect times, active and inactive QU curves and PU curves. It is adjustable through special software.
If needed, please contact after-sales. To obtain software manuals, you can download them from
the official website or contact after-sales.
5.5.1 PF Power Curve Mode
PF power curve mode can be modified by Modbus communication method, specifically according
to the machine Modbus address and Modbus register value, according to the set range to set the
corresponding value.
A
B
C
Power, (%P/P
rated
)
1.0
0.95
0.95
0%
25%
50%
75%
100%
cosФ
LEGEND:
cosФ
LEADING
LAGGING
5.5.2 PU Curve Mode
The PU curve mode can be modified by Modbus communication method, specifically according
to the machine Modbus address and Modbus register value, according to the set range to set the
corresponding value.
PF Power Curve Mode
Function
PF curve mode enable or disable
B power factor
C power factor
Default value (Australia)
0
50 (50%)
90 (90%)
Default value (New Zealand)
0
50 (50%)
90 (90%)
Setting range
“0”or“1”
30~80
90~100
Register
40600
40603
40606
V1
V2
V3
V4
100%
80%
60%
40%
20%
0%
200
210
220
230
240
250
260
270
V1
V2
V3
V4
100%
80%
60%
40%
20%
0%
200
210
220
230
240
250
260
270
POWER, P/Prated%
POWER, P/Prated%
Example curve for a volt-watt response mode (Australia)
Example curve for a volt-watt response mode (New Zealand)
Please press the "Enter" over 3 seconds to save the setting.