G30 Generator Protection System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
6.2.20 PARALLEL REDUNDANCY PROTOCOL (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
PATH: ACTUAL VALUES
STATUS
PRP
The G30 Generator Protection System is provided with optional PRP capability. This feature is specified
as a software option at the time of ordering. See the
Order Codes
section in chapter 2 for details.
TOTAL RECEIVED PORT A
is a counter for total messages received (either from DANPs or from SANs) on Port A.
TOTAL RECEIVED PORT B
is a counter for total messages received (either from DANPs or from SANs) on Port B.
TOTAL ERRORS
is a counter for total messages received with an error (bad port code, frame length too short).
MISMATCHES PORT A
is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
MISMATCHES PORT B
is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
PRP
Total Rx Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Rx Port B:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Errors:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port B:
Range: 0 to 4G, blank if PRP disabled
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...