48
E VOLUTI ON S E R I E S E9 0 0 0
M OTO R CO N T R O L C EN T ER
Electronic overload for circuit breaker and
fused controllers
The tripping current is 120% of the dial setting.
For continuous-rated motors with a service factor
of 1.15 to 1.25, set the dial to the motor full-load
current. For continuous-rated motors with a
service factor of 1.0, set the dial to 0.9 of the motor
full-load current. Refer to GEH-6430 or 6431
before energizing.
Catalog numbers of electronic overloads
for various sizes of NEMA starters and
current ranges
IEC style overload relays
C2000 contactor CLNCJ type RT overload relay
for 1/2X starter
Provide short-circuit protection in accordance with
NEC Article 430 or CE Code Part 1.
Tripping current is 120% of Dial setting. Motors
with 1.15-1.25 service factor, set dial to motor
FLA Motors with 1.0 service factor, set dial
to 0.9 motor FLA.
Catalog numbers of electronic overloads
for various sizes of NEMA starters and
current ranges.
NEMA
Size
FLA
Range in
Amps
Catalog
Number
Breaker Frame and Type
1
0.8 to 1.59
CR324CXD
E Mag. and Thermal Mag.
1
1.6 to 3.19
CR324CXE
E Mag. and Thermal Mag.
1
3.2 to 6.49
CR324CXF
E Mag. and Thermal Mag.
1
6.5 to 12.8
CR324CXG
E Mag. and Thermal Mag.
1
13 to 27
CR324CXH
E Mag. and Thermal Mag.
2
13 to 25.6
CR324DXG
E Mag. and Thermal Mag.
2
26 to 49.9
CR324DXH
E Mag. and Thermal Mag.
2
50 to 100
CR324DXJ
E Mag. and Thermal Mag.
3
17 to 34.9
CR324FXK
E Mag. and Thermal Mag.
3
35 to 64.9
CR324FXL
E Mag. and Thermal Mag.
3
65 to 90
CR324FXM
E Mag. and Thermal Mag.
4
17 to 34.9
CR324FXK
E,F and G Mag. and
Thermal Mag.
4
35 to 64.9
CR324FXL
E,F and G Mag. and
Thermal Mag.
4
65 to 135
CR324FXM
E,F and G Mag. and
Thermal Mag.
5¹
32 to 64.0
CR324GXN G Mag. and Thermal Mag.
5¹
65 to 129.9
CR324GXP G Mag. and Thermal Mag.
5¹
130 to 270 CR324GXQ G Mag. and Thermal Mag.
6²
130 to 259.9
CR324HXS
E,F and G Mag. and
Thermal Mag.
6²
260 to 540
CR324HXT
K Mag. and Thermal Mag
Current
Range
Max
CB
Cat.
No.
Class
Cat.
No.
Class
Lug/
Wire
Size
Torque
(in-lbs)
0.4-.65
15 RTN1D
10 RT12D
20 #14-8
14-20
0.65-1.1
15 RTN1F
10 RT12F
20 #14-8
14-20
1-1.5
15 RTN1G
10 RT12G
20 #14-8
14-20
1.3-1.9
15 RTN1H
10 RT12H
20 #14-8
14-20
1.8-2.7
15 RTN1J
10 RT12J
20 #14-8
14-20
2.5-4.1
15 RTNIK
10 RT12K
20 #14-8
14-20
4.0-6.3
15
RTNIL
10 RT12L
20 #14-8
14-20
5.5-8.5
15
RTNIM
10 RT12M
20 #14-8
14-20
8.0-12
30
RTNIN
10 RT12N
20 #14-8
14-20
10.0-16
35
RTNIP
10 RT12P
20 #14-8
14-20
14.5-18
40
RTNIS
10 RT12S
20 #14-8
14-20
17.5-22
50
RTNIT
10 RT12T
20 #14-8
14-20
NEMA
Size
FLA Range
in Amps
Catalog
Number
Max. Fuse in Amps
1
0.8 to 1.59 CR324CXD
Time-Delay
Class RandJ
30
Time-Delay
Class J 60
1
1.6 to 3.19 CR324CXE
1
3.2 to 6.49 CR324CXF
1
6.5 to 12.8 CR324CXG
1
13 to 27 CR324CXH
2
13 to 25.6 CR324DXG
60
100
2
26 to 49.9 CR324DXH
2
50 to 100 CR324DXJ
3
17 to 34.9 CR324FXK
100
200
3
35 to 64.9
CR324FXL
3
65 to 90 CR324FXM
4
17 to 34.9 CR324FXK
200
400
4
35 to 64.9
CR324FXL
4
65 to 135 CR324FXM
5¹
32 to 64.0 CR324GXN
400
600
5¹
65 to 129.9 CR324GXP
5¹
130 to 270 CR324GXQ
6²
130 to 259.9 CR324HXS
600
Class L
1200
Opening of the branch-circuit protective device
may be an indication that a fault current has been
interrupted. To provide continued protection
against £re or shock hazard, examine all current-
carrying parts and other components of the motor
controller and replace any damaged components. If
heater burnout occurs, the complete overload relay
must be replaced.