CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS
76
EPM 5000 series Advanced Power Meters
GE Multilin
12.5: Group 6, Functions 0–5—LM1/LM2 Set Limits and Relay Triggers for
Over/Under %THD Conditions
LM1 LED
LM2 LED
SWITCH 1
ABOVE/BELOW
SWITCH 2
RELAY 1
SWITCH 3
RELAY 2
LEVEL
ON
OFF
Digit Up
Digit Up
Digit Down
012.0
OFF
ON
Digit Down
Digit Down
Digit Up
009.0
Table 12.9
: Group 6—Example for Function 0
So, if THD exceeds 12%, LM1 is triggered and Relay 1 is enabled.
If THD falls below 9%, LM2 is triggered and Relay 2 is enabled.
12.6: Limits or Relays Programming Procedure
NOTE
: The procedure for programming any limit or relay for each group is identical. The example below
signifies the exact procedure for programming a Limit/Relay for GROUPS 4–6.
—Group 4 is used as an example.
NOTE:
Press
MAX/MIN/LIMITS
at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
GROUP
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
FUNCTION
RELAY
LIMIT
SWITCHES
VALUE
Step 1:
a.
Enter Group Level of Programming Mode
(see Chp. 8).
b.
Press
MAX/MIN/LIMITS
until
4.
appears in upper
display.
c.
Press
AMPS
to activate the Group.
Step 2:
a.
Press
MAX/MIN/LIMITS
to select desired Function.
!
Middle display provides the currently selected value
for whether to trip
above
or
below
, activate Relay 1
and activate Relay 2.
Left Switch: UP position indicates above tripping
value for lower display’s value. DOWN position
indicates below tripping.
Middle Switch: UP position sets Relay 1 to trip.
DOWN position doesn’t activate Relay 1 when limit
condition exists.
Right Switch: Same as Middle Switch , regarding
Relay 2.
b.
Press
VOLTS
to toggle between LM1 and LM2
settings.
!
The LM1 or LM2 annunciator indicates the limit
being displayed.
Содержание EPM 5300
Страница 2: ......
Страница 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin...