CHAPTER 5: OVERVIEW
30
EPM 5000 series Advanced Power Meters
GE Multilin
5.5: Accessing Max/Min Values
Max/min values represent the highest and lowest average demand over a user programmable time period
known as the
Integration Interval
. The readings are calculated using a rolling average technique. Each
second, a new reading is used to calculate the max/min; the last reading of the interval is dropped off.
The highest max during an averaging period is stored until the user resets the max/min. This is similar to
amp demand meters. It is commonly referred to as Thermal Demand.
To access a max/min value while displaying a desired measurement, press
MAX/MIN/LIMITS
—once for
the max value; twice for the min. Examples given below are for voltage and current phases. Use the
same procedure for all other parameters.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a.
To select the Volts category,
press
VOLTS
.
!
The display blanks and all
annunciators glow, confirming
selection.
Step 2:
a.
Press
PHASE/NEXT
for the
desired phase.
Step 3:
a.
Press
MAX/MIN/LIMITS
once
to view the maximum reading for
Volts C-N.
!
The display blanks and
momentarily indicates the max
value.
To access KW, KVAR and PF negative measurements indicating leading current, press
MAX/MIN/LIMITS
five times for negative max and six times for negative min.
5.6: Resetting Values
Use the reset function if a new value is desired. It is available in two different modes.
1.
UNPROTECTED MODE
: Allows quick and easy resetting of max/min values.
2.
PROTECTED MODE
: Prevents unauthorized resetting the max/min and totaled power functions.
Note: Even if the unprotected mode is selected during programming, the KWH and negative KWH
are always in protected mode. The following examples are for the max/min.
Содержание EPM 5300
Страница 2: ......
Страница 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin...
Страница 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin...