CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET RELAYS
GE Multilin
EPM 5000 series Advanced Power Meters
81
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
!
Middle and Lower display indicate FUNCTION
0
settings.
See Chapter 14 to exit.
13.4: Group 7, Function 1—Percentage Voltage Phase Imbalance
To change the percentage voltage phase imbalance:
NOTE:
Press
MAX/MIN/LIMITS
at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a.
Enter Group Level of Programming Mode
(see Chp. 9).
b.
Press
MAX/MIN/LIMITS
until
7.
appears in upper
display.
c.
Press
AMPS
to activate the Group.
Step 2:
a.
Press
MAX/MIN/LIMITS
until
71.
appears in upper
display.
!
Middle display indicates the Trip Relay 1 and Trip
Relay 2 settings.
!
Lower display indicates the percentage of Voltage
Phase Imbalance.
Содержание EPM 5200
Страница 2: ......
Страница 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin ...