CHAPTER 10: PROGRAMMING GROUP 1
62
EPM 5000 series Advanced Power Meters
GE Multilin
10.2: Group 1, Function 1—Amperage Full Scale
CT T
YPE
FULL
SCALE
Direct Input
05.00 A
600/5 0600
A
1000/5 1000
A
2000/5 2000
A
3000/5 03.00
KA
5000/5 05.00
KA
Table 10-3
: Full Scale Settings for Amps
Also note that the meter reads with digital accuracy to a 2000 count range. Thus all CT and PT full scale
settings in the meter should reflect that limitation. The table above shows the proper settings.
To change the Full Scale Settings:
NOTE
: Press
MAX/MIN/LIMITS
at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a.
Enter Group Level of Programming Mode
(see Chp. 8).
b.
Press
MAX/MIN/LIMITS
until
1.
appears in
upper display.
Step 2:
a.
Press
AMPS
to activate the Group.
b.
Press
MAX/MIN/LIMITS
until
11.
appears in
upper display.
!
Middle display indicates Scale Factor Setting.
!
Lower display indicates Full Scale.
Содержание EPM 5200
Страница 2: ......
Страница 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin ...
Страница 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin ...