6
Installing Flux Shifter Reset Bracket
Replace existing reset bracket with new bracket as shown in
Figure 3 and Figure 4 below:
Install Flux Shifter Asm
The Flux shifter mounting location is shown in Figure 5 below:
Mount Flux Shifter assembly to breaker frame as shown in
figures 6 and 7.
Install the Reset Link between the reset Bracket and Flux
Shifter Assembly as shown in Figure 8.
Adjust Flux Shifter to breaker latch with breaker in the charged
position. Set the .031 dimension as shown in figure 8 and lock
with Jam nut.
Old Reset Asm
to be removed
New Reset Asm to
replace old Asm
Existing hardware
to be used to install
new reset Asm
Figure 3: Old and New Reset Assembly
Breaker
Cross bar
Existing
hardware
Figure 4: Installed Reset Assembly
These 2 existing holes are to be
used to mount Flux shifter Asm
to side of breaker mech
Figure 5: Flux Shifter mounting location
MTG hardware 1/4 x3/4 Long Hex Head
and Split LK Washer
F/S MTG
spacers
positioned
as shown to
space F/S
assy away
from
breaker
mech side
frame
Reset Link
Jam Nut
Set .031
Figure 6: Flux Shifter mounting
Figure 7: Flux Shifter mounting
Figure 8: Installing Reset Link