background image

 

14 

 

the electrical connections may not be properly tightened or 
it could also indicate improper contact wipe. 

 

4.

  To verify that the breaker has been properly retrofitted, 

perform a primary injection test on each phase. This test 
will check the CTs, bus, wiring harness, flux shifter, and 
trip unit as a complete system. 

a.

  A high-current, low-voltage power supply should be 

connected across each line and load terminal to simulate 
an overcurrent fault. 

b.

  Set the long-time trip at 0.5 to minimize the breaker 

stress. 

c.

  When ground fault is installed, the test can be 

performed by wiring two adjacent poles in series or by 
using the GE Digital Test Kit, cat. no. TVRMS2. This 
will prevent the breaker from tripping because of an 
unbalanced current flow. For Entelliguard TU use 
GTUTK20. 

CAUTION:

 Do not attempt to use GE Test Kit cat. no. 

TVTS1 or TVRMS on Entelliguard trip unit and do not use 
GTUTK20 on MVT trip unit. 

Trouble-Shooting 

When malfunctioning is suspected, first examine the breaker 
and its power system for abnormal conditions such as the 
following: 

•  The breaker is not tripping in response to overcurrent 

conditions or incipient ground faults. 

•  The breaker is remaining in a trip-free state because of 

mechanical interference along its trip shaft. 

•  The shunt trip (if present) is activating improperly. 

Nuisance Tripping on Ground Fault-Equipped Breakers 

When nuisance tripping occurs on breakers equipped with 
ground fault trip, a probable cause is the existence of a false 
ground signal. Each phase sensor is connected to summing 
circuitry in the trip unit. Under no-fault conditions on three-
wire load circuits, the currents add to zero and no ground signal 
is developed. This current sum is zero only if all three sensors 
have the same electrical characteristics. If one sensor differs 
from the others (such as by a different rating or wrong tap 
setting), the circuitry can produce an output sufficient to trip the 
breaker. Similarly, a discontinuity between any sensor and the 
trip unit can cause a false trip signal. 

The sensors and their connections should be closely examined 
if nuisance tripping is encountered on any breaker whose 
Entelliguard, MicroVersaTrip Plus or MicroVersaTrip PM trip 
unit has previously demonstrated satisfactory performance. 
After disconnecting the breaker from all power sources, 
perform the following procedure: 

 

1.

  Check that all phase sensors are the same type (current 

range). 

 

2.

  Verify that the tap settings on all three phase sensors are 

identical. 

 

3.

  Verify that the wiring harness connections to the sensors 

have the proper polarity (white lead to common, black lead 
to tap), as shown in the cabling diagrams1. 

 

4.

  On ground fault breakers serving four-wire loads, check 

that the neutral sensor is properly connected, as indicated 
in Figure 27. In particular, check the following: 

a.

  Verify that the neutral sensor has the same rating and 

tap setting as the phase sensors. 

b.

  Verify continuity between the neutral sensor and its 

equipment-mounted secondary disconnect block. Also 
check for continuity from the breaker-mounted neutral 
secondary disconnect block through to the trip unit 
wiring harness connector. 

c.

  If the breaker’s lower studs connect to the power 

source, then the neutral sensor must have its load end 
connected to the source. 

d.

  Verify that the neutral conductor is carrying only the 

neutral current associated with the breaker’s load 
current (the neutral is not shared with other loads). 

 

5.

  If the preceding steps fail to identify the problem, then 

measure the sensor resistances. The appropriate values are 
listed in Table 1. Since the phase and neutral sensors are 
electrically identical, their resistances should agree closely. 

 

Breaker 

CT Rating, A 

Resistance, ohms 

LA-4000-Blue 

4000 

29–39 

 

 

 

 

 

 

 

 

 

Table 1. CT resistance values. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание Entelliguard TU Conversion Kit

Страница 1: ...signed and tested to conform to ANSI Standard C37 59 allowing the retrofitter to properly install the kit and acceptance test the breaker This publication covers installation of Entelliguard MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits on Allis Chalmers Siemens Allis and Siemens LA 4000 low voltage power circuit breakers Each Conversion Kit contains all the components needed to conver...

Страница 2: ... Installing ththe Trip Unit Wiring Harness Page 7 Installing the Trip Unit Mounting Bracket Page 9 Installing the Current Sensors Page 10 Installing the Communications Harness Page 11 Section 5 Installing the Trip Unit Page 11 Section 6 Four Wire Ground Fault Option Page 12 Section 7 Testing and Trouble shooting Page 13 Testing Pages 13 Trouble Shooting Page 14 Nuisance Tripping on Ground Fault Eq...

Страница 3: ...or Page 7 10 36 pin connector adapter bracket Page 7 11 Adapter bracket locking tabs Page 8 12 Installing the push nuts ono the guide pins Page 8 13 Locking tabs on mounting plate Page 8 14 Trip unit bracket mounting Page 9 15 Securing trip unit bracket Page 9 16 Position of current sensors Page 10 17 Installing current sensors Page 10 18 Installing wire harness Page 10 19 Caution label to be appl...

Страница 4: ... breakers use high speed stored energy spring operating mechanisms The breakers and their enclosures contain interlocks and safety features intended to provide safe proper operating sequences For maximum personnel protection during installation operation and maintenance of these breakers the following procedures must be followed Failure to follow these procedures may result in personal injury or p...

Страница 5: ...s to be installed on a fused breaker LAF series remove the fuse structure from the upper line studs to allow easier access to the load studs Additional work may be required to install kit into fused breaker 3 Loosen the three Allen head screws securing each of the primary disconnects to the line upper and load lower studs and remove the primary disconnects 4 Remove the wires from the original curr...

Страница 6: ...icroVersaTrip Plus and MicroVersaTrip PM and conversion kit The components provided with the kit are shown in Fig 2 Mounting Plate Figure 2 Components supplied with the conversion kit Current Sensor LA4000 Blue Wiring Harness Trip Unit Connector Hardware Flux Shifter Assembly Programmer Bracket Assembly ...

Страница 7: ...31 dimension as shown in figure 8 and lock with Jam nut Old Reset Asm to be removed New Reset Asm to replace old Asm Existing hardware to be used to install new reset Asm Figure 3 Old and New Reset Assembly Breaker Cross bar Existing hardware Figure 4 Installed Reset Assembly These 2 existing holes are to be used to mount Flux shifter Asm to side of breaker mech Figure 5 Flux Shifter mounting loca...

Страница 8: ...ovide protection If the converted breaker is energized or primary injected with the mounting plate not installed or installed improperly damage will result to the trip unit wire harness 36 pin connector and current sensors Failure to adhere to these instructions will void all warranties 2 Slide the adapter bracket onto the 36 pin connector as shown in Figure 10 Be sure that the beveled corners of ...

Страница 9: ...own in Figure 12 until the assembly is held firmly against the trip unit mounting plate 5 While holding the adapter bracket and connector assembly firmly in place against the mounting plate bend the two locking tabs on the mounting plate into the mating notches on the adapter bracket using a screwdriver as shown in Figure 13 Figure 12 Installing the push nuts onto the guide pins Figure 13 Locking ...

Страница 10: ...ip Unit mounting bracket as shown in figure 14 and secure in this position with locking plate shown in Figure 15 Hardware 20 Hex Hd Lg Plain Washer Split Lk Washer Locking Plate Assy Figure 14 Trip Unit bracket mounting Figure 15 Securing Trip Unit bracket ...

Страница 11: ...he breaker B is the center C is the left and are also cut to the appropriate lengths Attached the white wire to the terminal marked white Reattach the primary disconnect assemblies to all the studs To aid in reinstalling disconnect 3 1 4 20 long screws are supplied in hardware package These screws are used only to help force disconnects onto their corresponding studs Disconnects are to be secured ...

Страница 12: ... DC to the trip unit Power supply of 24V DC is essential for advanced functions of the trip unit such as backlight display status LED indicator event log etc SECTION 5 INSTALLING THE TRIP UNIT Use the following procedure to install the trip unit 1 Pull out the locking lever on the trip unit mounting plate until it snaps into the open position as shown in Figure 12 2 Carefully line up the 36 pin co...

Страница 13: ... bus or cable compartment in the equipment Figure 27 shows the sensor outlines for the 3000 A through 4000 A frame sizes 2 Connect the neutral sensor wire harness to the correct taps on the sensor To maintain the same polarity as the phase sensors connect the white wire to the common terminal black to the tap 3 Route the wires through the equipment and connect to the two pin connector on the trip ...

Страница 14: ...e converted breaker each phase of the breaker should be primary injected with a current level of about 10 but no more than 20 of the CT rating During the application of test current activate the trip unit screen by depressing the battery button on the trip unit face and check that the test current is displayed on the screen for each phase tested If the trip unit fails to display the test current s...

Страница 15: ...or differs from the others such as by a different rating or wrong tap setting the circuitry can produce an output sufficient to trip the breaker Similarly a discontinuity between any sensor and the trip unit can cause a false trip signal The sensors and their connections should be closely examined if nuisance tripping is encountered on any breaker whose Entelliguard MicroVersaTrip Plus or MicroVer...

Страница 16: ...t cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company ...

Отзывы: