
F-07 Accel Time 1
Range:
Function:
10.00
s
*
[1.00
- 3600
s]
Enter the accel time, that is the acceleration time
from 0 RPM–
. Select a
accel time such that the output current does not
exceed the current limit in
during ramping. See decel time in
par
.
F
− 07 =
t
acc
×
n
nom
par
.
P
− 06
ref
RPM
s
F-08 Decel Time 1
Range:
Function:
20.00
s
*
[1.00 -
3600 s]
Enter the decel time, that is the deceleration
–0 RPM.
Select a decel time preventing overvoltage
from arising in the inverter due to regenerative
operation of the motor. The ramp-down time
should also be long enough to prevent that
the generated current exceeds the current limit
set in
. See accel
time in
.
par
.
F
− 08 =
t
dec
×
n
nom
par
.
P
− 06
ref
RPM
s
F-09 Torque Boost
This parameter is not visible on the LCP.
Range:
Function:
100 %
*
[0 -
300 %]
NOTICE
has no
effect when
[1] PM, non-salient SPM
.
Enter the % value to compensate voltage in
relation to load when the motor is running at
low speed, and obtain the optimum U/f
characteristic. The motor size determines the
frequency range within which this parameter is
active.
Motor size [kW]
Change–over [Hz]
0.25–7.5
<10
11–45
<5
55–550
<3–4
Table 3.3 Low Speed Load Compensation
Illustration 3.4 Low Speed Load Compensation
3.2.2 F-1# Fundamental Parameters 1
NOTICE
When using multiple motors, the electronic thermal relay
on the frequency converter cannot be used to provide
individual motor protection. Supply a separate motor
overload for each motor.
F-10 Electronic Overload
Option:
Function:
The frequency converter determines the
motor temperature for motor overload
protection in 2 different ways:
•
Via a thermistor sensor connected
to 1 of the analog or digital
inputs (
). See
chapter 3.2.3.1 PTC Thermistor
•
Via calculation of the thermal
load, based on the actual load
and time. The calculated thermal
load is compared with the rated
motor current I
M,N
and the rated
motor frequency f
M,N
. The
calculations estimate the need for
a lower load at lower speed due
to less cooling from the fan
incorporated in the motor. See
chapter 3.2.3.2 Electronic Thermal
.
•
Via a mechanical thermal switch
(Klixon type). See
. The ETR
provides class 20 motor overload
protection in accordance with
NEC.
Parameter Description
36
03/2016 All rights reserved.
DET-620D
3
3