K-50 Keypad Copy
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
[0]
*
No copy
[1]
All to Keypad Copies all parameters in all set-ups from the
frequency converter memory to the keypad
memory. For service purposes, copy all
parameters to the keypad after commis-
sioning.
[2]
All from
Keypad
Copies all parameters in all set-ups from the
keypad memory to the frequency converter
memory.
[3]
Size indep.
From Keypad
Copies only the parameters that are
independent of the motor size. Use the
latest selection to program several frequency
converters with the same function without
disturbing motor data which are already set.
[10]
Delete LCP
copy data
K-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy to set-
up 1
Copies all parameters in the present
programming set-up (defined in
) to set-up 1.
[2]
Copy to set-
up 2
Copies all parameters in the present
programming set-up (defined in
) to set-up 2.
[3]
Copy to set-
up 3
Copies all parameters in the present
programming set-up (defined in
) to set-up 3.
[4]
Copy to set-
up 4
Copies all parameters in the present
programming set-up (defined in
) to set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up
to each of the set-ups 1 to 4.
3.1.7 K-6# Password Protection
K-60 Main Menu Password
Range:
Function:
100
*
[-9999 -
9999]
Define the password for access to the Main
Menu via the [Main Menu] key. If
parameter K-61 Access to Main Menu w/o
is set to
[0] Full access
, this parameter
is ignored.
K-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter K-60 Main Menu Password
[1]
Keypad: Read only Prevents unauthorized editing of
Main
Menu
parameters.
[2]
Keypad: No access Prevents unauthorized viewing and
editing of
Main Menu
parameters.
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If
[0] Full access
is selected,
parameter K-65 Quick Menu Password
, and
parameter K-66 Access to Quick Menu w/o Password
are
ignored.
K-65 Quick Menu Password
Range:
Function:
200
*
[-9999 -
9999]
Define the password for access to Quick Start
Menu via the [Quick Menu] key. If
parameter K-66 Access to Quick Menu w/o
is set to
[0] Full access
, this parameter
is ignored.
K-66 Access to Quick Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter K-65 Quick Menu Password
.
[1]
Keypad: Read only Prevents unauthorized editing of Quick
Start Menu-parameters.
[2]
Keypad: No access Prevents unauthorized viewing and
editing of Quick Start Menu-parameters.
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If
parameter K-61 Access to Main Menu w/o Password
is set
to
[0] Full access
, this parameter is ignored.
K-67 Bus Password Access
Range:
Function:
0
*
[0 - 9999] Use this parameter to unlock the frequency
converter via network or DCT-10.
3.1.8 K-7# Clock Settings
Set the time and date of the internal clock. The internal
clock can be used for timed actions, energy log, trend
analysis, date/time stamps on alarms, logged data,
preventive maintenance, and so on.
Parameter Description