Parameter
[Units]
Parameter K-02 Motor Speed Unit
Parameter P-02 Motor Power [HP]
[Hp]
Parameter P-07 Motor Power [kW]
[kW]
Parameter F-05 Motor Rated Voltage
[V]
[Hz]
[A]
[RPM]
Parameter F-01 Frequency Setting 1
Parameter F-02 Operation Method
[s]
[s]
Parameter F-10 Electronic Overload
Parameter F-15 Motor Speed High Limit [Hz]
1)
[Hz]
Parameter F-16 Motor Speed Low Limit [Hz]
1)
[Hz]
Parameter F-17 Motor Speed High Limit [RPM]
[RPM]
Parameter F-18 Motor Speed Low Limit [RPM]
[RPM]
Table 2.1 Quick Set-up Parameters
1) The information shown in the display depends on the selections
made in parameter K-02 Motor Speed Unit and
parameter K-03 Regional Settings. The default settings of
parameter K-02 Motor Speed Unit and parameter K-03 Regional
Settings depend on which region of the world the frequency
converter is supplied to, but can be reprogrammed as required.
2.1.5 Macros
The Macros provide quick and easy access to all
parameters required for most HVAC applications including:
•
Most VAV and CAV supply and return fans.
•
Cooling tower fans.
•
Primary pumps.
•
Secondary pumps.
•
Condenser water pumps.
•
Other pump, fan and compressor applications.
How to access Macros - example
1.
Turn on the frequency converter (green LED
lights).
Illustration 2.15 Frequency Converter Turned On
2.
Press [Quick Menus].
Illustration 2.16 Quick Menu Selected
3.
Press [
▲
] and [
▼
] to scroll down to Fan Macros.
Press [OK].
Illustration 2.17 Scrolling to Function Set-up
How to Program
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
17
2
2