DMC490 Microgrid Controller Software Configuration Guide
44
Minimum Delay
Between Last Start
Up and First Shut
Down (Seconds)
This setting is the minimum delay between last starting
and the first stopping of dispatchable units.
10, 20, 30,
40, 50, 60
seconds
10 seconds
Storage Units Settings
Point Settings
Setting
Description
Range
Default
Time Interval
Between Discharging
Start Ups (Seconds)
This setting is the minimum delay between starting
discharging storage units.
10, 20, 30,
40, 50, 60
seconds
10 seconds
Time Interval
Between Charging
Shut Downs (Seconds)
This setting is the minimum delay between stopping
charging storage units.
10, 20, 30,
40, 50, 60
seconds
10 seconds
Time Interval
Between Discharging
Shut Downs (Seconds)
This setting is the minimum delay between stopping
discharging storage units.
10, 20, 30,
40, 50, 60
seconds
10 seconds
Time Interval
Between Charging
Start Ups (Seconds)
This setting is the minimum delay between starting
charging storage units.
10, 20, 30,
40, 50, 60
seconds
10 seconds