![GE Digital Energy LP 11U Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/ge/digital-energy-lp-11u/digital-energy-lp-11u_installation-and-user-manual_133037046.webp)
Digital Energy
™
LP Series
g
LP 5/6/8/10-11U installation drawings
Model Heat
dissipation
Linear load 240 Volt
Dimensions Air
flow
100%
load
Rel.
humidity
non-cond.
Altitude
(max 4000m)
Input wiring
Output wiring
100% load
50% load
h
w
d
Weight
Amb.
temp.
utility
volt.
120V
utility volt.
208V
utility volt.
240V
output
volt. 120V
output
volt. 208V
output
volt. 240V
LP-U W
Btu/hr
W
Btu/hr
Inch
Inch
Inch
Lbs
m3/hr
°F
m
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
5-11
571 1950 389 1329 26.8 12.3 28.7 295 660 14-104 <95
N.A.
10/6
10/6
8/10
10/6
10/6
6-11
661 2254 381 1300 26.8 12.3 28.7 295 660 14-104 <95
N.A.
8/10
10/6
8/10
10/6
10/6
8-11
948 3234 551 1882 26.8 12.3 28.7 386 660 14-104 <95
N.A.
6/14
8/10
6/14
8/10
8/10
10-11
1090 3719 556 1896 26.8 12.3 28.7 410 660 14-104 <95
N.A.
4/22
6/14
4/22
8/10
8/10
5-11/120
V 641 2187 425 1451 39.2 12.3 28.7 386 660 14-104 <95
6/14
N.A.
N.A.
8/10
10/6
10/6
6-11/120
V 744 2539 601 2051 39.2 12.3 28.7 386 660 14-104 <95
<1000, derating
12.5% per 1000
4/22 N.A. N.A. 8/10 10/6 10/6
Model
Minimum free space required
(Inches)
front side rear
Distance between mounting
holes (Inches)
Input overcurrent protection
(AMPS)
Output overcurrent protection (AMPS)
LP-U
x
y
z 120V 208V 240V 120V
(1 X)
120V
(2X)
208V 240V
5-11
4 2 8 7.24
22.76
7.48
35 30 40 20 25 20
5-11
/120V 4 2 8
7.24
22.76
7.48
60 40
20
25 20
6-11
4 2 8 7.24
22.76
7.48
40 35 50 25 30 25
6-11
/120V 4 2 8
7.24
22.76
7.48
70 50
25
30 25
8-11
4 2 8 7.24
22.76
7.48
60 45 70 35 40 35
10-11
4 2 8 7.24
22.76
7.48
70 60 80 40 50 40
Содержание Digital Energy LP 11U