Installation
2-3
September 2005
Wiring Configurations
Caution!
The DewPro system includes electronic components that
are susceptible to damage by static electricity. Use proper
handling procedures during the removal, installation, or
other handling of internal boards or devices.
Note:
If the DewPro is equipped with an optional display/user
interface, please refer to Chapter 4.
Figure 2-3 below illustrates various power supplies and displays for
use with the DewPro MMY31.
Figure 2-3: System Configuration, Various
Designing the Loop
When selecting a power supply, please note that the voltage at the +/-
terminal of the DewPro should not fall below 12 VDC. The maximum
loop resistance is an important measure for selection of the supply
voltage. Each device connected to the loop causes a voltage drop. For
instance, using a loop-powered display with an input impedance of
50
Ω
will cause a voltage drop of 1 VDC at 20 mA, using Ohm's law.
Connecting the loop to a PLC will cause a voltage drop across the
input.
When designing your loop, add up all voltage losses across the
devices connected to the loop and add 12 V. The sum will be the
minimum supply voltage required from the power supply. Calculate
with a 20% safety factor.
Sensing, such as Md102
Sensing
’
24 VDC (12...28 VDC)
Содержание DewPro MMY31
Страница 5: ...Chapter 1 ...
Страница 6: ...General System Information Unpacking and Inspection 1 1 Theory of Operation 1 3 ...
Страница 10: ...Chapter 2 ...
Страница 11: ...Installation Mounting the MMY31 cont 2 2 Wiring Configurations 2 3 ...
Страница 17: ...Chapter 3 ...
Страница 18: ...Troubleshooting The Loop Current is Out of Range 3 1 There Is No Current 3 1 ...
Страница 20: ...Chapter 4 ...
Страница 29: ...Chapter 5 ...