GE Multilin
D60 Line Distance Protection System
B-53
APPENDIX B
B.4 MEMORY MAPPING
B
7EC2
Dist Zbc Mag
0 to 655.35
ohm
---
F001
0
7EC3
Dist Zbc Ang
-359.9 to 0
degrees
0.1
F002
0
7EC4
Dist Zca Mag
0 to 655.35
ohm
0.01
F001
0
7EC5
Dist Zca Ang
-359.9 to 0
degree
0.1
F002
0
7EC6
Dist Zag Mag
0 to 655.35
ohm
0.01
F001
0
7EC7
Dist Zag Ang
-359.9 to 0
degree
0.1
F002
0
7EC8
Dist Zbg Mag
0 to 655.35
ohm
0.01
F001
0
7EC9
Dist Zbg Ang
-359.9 to 0
degree
0.1
F002
0
7ECA
Dist Zcg Mag
0 to 655.35
ohm
0.01
F001
0
7ECB
Dist Zcg Ang
-359.9 to 0
degree
0.1
F002
0
Neutral Overvoltage (Read/Write Grouped Setting) (3 Modules)
7F00
Neutral Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F01
Neutral Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F02
Neutral Overvoltage 1 Pickup
0 to 3.00
pu
0.001
F001
300
7F03
Neutral Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F04
Neutral Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F05
Neutral Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7F07
Neutral Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F08
Neutral Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F09
Neutral Overvoltage 1 Curves
0 to 3
---
1
F116
0 (Definite Time)
7F0A
Reserved (8 items)
0 to 65535
---
1
F001
0
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 Modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
700
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7F68
Auxiliary Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F69
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F6A
Reserved (7 items)
0 to 65535
---
1
F001
0
7F71
...Repeated for Auxiliary Undervoltage 2
7F82
...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules)
7FA0
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7FA1
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7FA2
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7FA3
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7FA4
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7FA5
Auxiliary Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7FA7
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7FA8
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7FA9
Reserved (8 items)
0 to 65535
---
1
F001
0
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
2 to 90
Hz
---
F001
0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
-55 to 125
C
1
F002
-55
81C1
Reserved Register T2
-55 to 125
C
1
F002
125
Table B–10: MODBUS MEMORY MAP (Sheet 45 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...