5-234
D30 Line Distance Protection System
GE Multilin
5.8 INPUTS AND OUTPUTS
5 SETTINGS
5
DIRECT INPUT 6 BIT NUMBER:
"2"
DIRECT OUT 2 OPERAND:
"
HYB POTT TX1
"
DIRECT OUT 3 OPERAND:
"
DIRECT INPUT 5
" (forward a message from 1 to 3)
DIRECT OUT 4 OPERAND:
"
DIRECT INPUT 6
" (forward a message from 3 to 1)
Signal flow between the three IEDs is shown in the figure below:
Figure 5–124: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip (
HYB POTT RX1
setting).
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS
a) OVERVIEW
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protec-
tion and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
TELEPROTECTION
TELEPROT INPUTS
TELEPROT INPUTS
TELEPROT INPUT 1-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 1-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 1-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 2-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
842717A1.CDR
UR IED 3
UR IED 2
UR IED 1
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 5
Содержание D30D00HCHF8AH6AM6BP8BX7A
Страница 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Страница 52: ...2 22 D30 Line Distance Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 96: ...3 44 D30 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 126: ...4 30 D30 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Страница 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Страница 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Страница 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Страница 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Страница 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Страница 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Страница 646: ...x D30 Line Distance Protection System GE Multilin INDEX...