• Inspect luminaire to confirm no damage has occurred
during transit.
• To avoid damage, do not impact or stack luminaire
after removal from packaging.
UNPACKING/HANDLING
1
2a. Surface Mount (Figure 1):
• Cut 8” x 8” square opening in underside of canopy.
• Remove cover plate knockout (1/2” or 3/4”) for desired
conduit diameter.
• Feed flex conduit through canopy opening and secure
to cover plate.
• Connect fixture leads to service leads from conduit in
accordance Section 3 “Wiring.”
• Secure cover plate to top of fixture with four #10
screws provided.
• Secure fixture to underside of canopy with four #10
toggle bolts (not provided)
2b. J-Box Mounting (Figure 2):
• Install J-Box mounting plate to grounded J-Box with
#8 screws (not provided).
• For 347 volt units, install tether with #10 screws
included in fixture package to hole in J-Box mounting
plate and housing (120-277 volt units do not require
tether).
• Connect fixture leads to service leads from inside the
J-Box in accordance with Section 3” Wiring.”
• Route tether (if required) in drain hole slot when
closing fixture to J-Box mounting plate.
• Secure fixture to J-Box mounting plate with #10
screws provided.
2c. Pendant (Rigid Conduit) Mounting (Figure 3):
• Feed service wires through conduit mounting plate
and thread plate onto rigid conduit.
• Tighten set screw into conduit to lock.
• For 347 volt units, install tether with #10 screws
included in fixture package to hole in conduit mounting
plate and housing (120-277 volt units do not require
tether, but #10 screw must be installed in hole in
conduit mounting plate).
• Connect fixture leads to service leads from rigid
conduit in accordance with Section 3 ”Wiring.”
• Route tether (if required) in drain hole slot when closing
fixture to conduit mounting plate.
• Secure conduit mounting plate to back of fixture with
four #10 screws provided.
MOUNTING
2
Risk of injury or damage. Unit will fall if not installed
properly. Follow installation instructions.
8 in. x 8 in.
CUTOUT
FLEX CONDUIT
COVER PLATE
#10 SCREWS
PROVIDED
#10 TOGGLE BOLT
NOT PROVIDED
J'BOX
#8 SCREWS
NOT PROVIDED
J'BOX MOUNTING PLATE
#10 SCREW
TETHER
TETHER
ROUTING
#10 SCREW
PROVIDED
TETHER
ROUTING
CONDUIT
MOUNTING PLATE
WARNING
Figure 1
Figure 2
Figure 3