WARNING
Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous.
Certifications are based on the use of approved cables only. Currently available approved cables are BHGE Reuter-
Stokes RS-E2-0279 and GE AE 07482SOCNL44820.
Do not attempt to disassemble the sensor. Sensors are not repairable. Breaching the seal of the sensor will cause
loss of the inert fill gas and render the sensor unusable.
Do not remove the sensor by wrenching on the body. Always use the 1 3/8 inch mounting nut. Wrenching on the
body may breach the seal. Breaching the seal of the sensor will cause loss of the inert fill gas and render the sensor
unusable.
Do not install a sensor that has a cracked window, damaged threads or one that has been disassembled.
Do not install or remove the flame sensor from the sight tube with the cooling coils attached to the flame sensor.
Sensor disassembly and malfunction may occur, possibly resulting in a false Flame On signal.
CAUTION
The operating temperature range of the Flame Sensor is
-40°C to 150°C
.
Do not
attempt to work on the Flame
Sensor until it has reached a safe handling temperature.