GE Baker Hughes Reuter-Stokes Flame Tracker... Скачать руководство пользователя страница 15

FS-9006OM 

– REV K 

 

 
 

MAINTENANCE 

 

4.1 WARNING 

 

Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous. 

 

4.2 CAUTION 

 

The operating temperature range of the Flame Sensor is -40°C to 150°C.  Do not attempt to work on the Flame 

Sensor or the cable until they have cooled to a safe handling temperature. 

The Flame Sensor output will deteriorate as the lens becomes dirty.  It is recommended, when initially installed, 

that the signal level be recorded during normal operation.  During subsequent running, the signal level should 
be compared with the initial values.  If a significant reduction in the signal level is noticed, then it is recommended 
that  the  lens  be  cleaned  at  the  next  opportunity  (with  the  turbine  shut  down  and  cold).  Clean  the  lens  with 
isopropyl alcohol or other residue free solvent compatible with Sapphire. In order to reduce the risk of galling, 
an anti-seize compound should be applied to the mounting thread prior to reinstallation of the sensor. 

TROUBLESHOOTING 

 

5.1 WARNING 

 

  Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous. 

 

5.2 CAUTION 

 

The  operating  temperature  range  of  the  Flame  Sensor  is 

-40°C  to  150°C

.   

Do  not 

attempt to work  on  the 

Flame Sensor or the cable until they have cooled to a safe handling temperature. 

 

PROBLEM 

CAUSE 

SOLUTION 

 

 

 

No current flows 

Reversed polarity 

Change polarity 

Low sensitivity during 
checkout or operation 

Dirty lens 
Grounded cable 

Clean lens (Section 4.0) 
Check cable for grounds 

Low flame intensity signal 
during operation 

Misalignment of the sensor 
mount 

Check the squareness of all 
flanges and pipes of the sensor 
mount.  Verify that the senor has a 
clear view of the flame. 

 

Obstructions in the line of 
sight 

Look for washers, or valves that 
may restrict the diameter of the 
sight tube.  

 

Condensation on the lens 

Over cooling can cause moisture 
to condense on the lens and 
reduce the signal.  Reduce the 
cooling until the condensation 
clears up and the signal returns to 
normal. 

 

Содержание Baker Hughes Reuter-Stokes Flame Tracker...

Страница 1: ...FS 9006 GE 07482SOCNL44819P01 Operation and Maintenance Manual FS 9006OM Rev K November 2017 www gemeasurement com A trademark of Baker Hughes a GE company LLC 2017 Baker Hughes a GE company All righ...

Страница 2: ...G AS WELL AS WARRANTIES IMPLIED FROM A COURSE OF PERFORMANCE OR COURSE OF DEALING THE MATERIALS IN THIS MANUAL WILL BE ERROR FREE OR THAT THE MATERIALS IN THIS MANUAL WILL BE COMPLETE ACCURATE OR TIME...

Страница 3: ...4 WRTR L Lombardo REV E DATE 06 25 10 ECN 40293054 WRTR R Martin REV F DATE 04 24 13 ECN 77469075 WRTR J Hashmi REV G DATE 12 18 15 ECN 500000157848 WRTR J Hashmi REV H DATE 02 22 16 ECN 500000204318...

Страница 4: ...Ta 235 C T2 with cooling coil South Korea KTL hazardous area mark Customs Union hazardous area mark China hazardous area mark Brazil INMETRO hazardous area mark India hazardous area approved Taiwan ha...

Страница 5: ...by wrenching on the body Always use the 1 3 8 inch mounting nut Wrenching on the body may breach the seal Breaching the seal of the sensor will cause loss of the inert fill gas and render the sensor u...

Страница 6: ...TERCONNECTING CABLE RS E2 0279PXXX OR 362A1053PXXX 2 1 2 REFERENCE 3 1 3 GENERAL DESCRIPTION 4 2 SENSOR 4 3 INSTALLATION 5 3 1 MECHANICAL 5 3 2 ELECTRICAL 7 3 3 CONNECTOR PINOUT 8 3 4 SENSOR CHECKOUT...

Страница 7: ...s III size 15 5 pin Sensor Silicon Carbide photodiode Window Sapphire Operating Sensitivity 5 mA 1x1010 photons in2 sec 310 nm Output 4 20 mA dc Max 21 mA Response Time 25 milliseconds Power Requireme...

Страница 8: ...e 1 02 mm 19 strand nickel plated copper Insulation Teflon PTFE Shield Jacket 36 gauge 0 127 mm nickel plated copper braid Extruded PFA Armor Stainless steel braid Connector MIL C 38999 series III she...

Страница 9: ...FS 9006OM REV K 3 1 2 REFERENCE...

Страница 10: ...n a number of GE gas turbine installations 2 SENSOR Figure 1 is a block diagram of the SiC Flame Sensor The sensor has a sapphire window that is transparent to UV light and can withstand the compresso...

Страница 11: ...1 5 m sec or greater at a temperature of 50 F 10 C or less above outside ambient Under these conditions the sensors will operate at outside ambient temperatures up to 140 F 60 C Air cooling with press...

Страница 12: ...pplied below the 2nd thread If Never Seez is applied to the face of the sight tube upon heating it can fog the window of the Flame Sensor 3 Inspect the window and clean with Isopropanol soaked swab If...

Страница 13: ...er or to earth ground at any location The inner shields should be individually jumpered through all junction boxes and connected to the proper ground terminal at the Controller The polarity of the cab...

Страница 14: ...see zero flame intensity signal and with a flashlight to see a positive reading With no light the reading should be 3 7 to 4 1 milliamps while with most flashlights the reading should be above 8 milli...

Страница 15: ...ize compound should be applied to the mounting thread prior to reinstallation of the sensor 5 TROUBLESHOOTING 5 1 WARNING Do not disconnect connector while circuit is energized or live unless area is...

Отзывы: