CHAPTER 5: SETTINGS
TESTING
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-277
5
•
If set to “Open,” the input is forced to report as opened (Logic 0) while the operand selected by
TEST MODE FORCING
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
•
If set to “Closed,” the input is forced to report as closed (Logic 1) while the operand selected by
TEST MODE FORCING
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
5.11.4 Force contact outputs
SETTINGS
TESTING
FORCE CONTACT OUTPUTS
The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
While in Forcible test mode, the relay contact outputs can be pre-programmed to respond in the following ways:
•
If set to “Normal,” the contact output remains fully operational. It operates when its control operand is logic 1 and
resets when its control operand is logic 0.
•
If set to “Energized,” the output closes and remains closed while the operand selected by the
TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
•
If set to “De-energized,” the output opens and remains opened while the operand selected by the
TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
•
If set to “Freeze,” the output retains its position at the instant before the
TEST MODE FUNCTION
was Forcible and the
operand selected by the
TEST MODE FORCING
setting was On, regardless of later changes in the status of the operand
configured to control the output contact. While the selected operand is Off, the output behaves as it does when in
service.
On restart, the
TEST MODE FORCING
setting and the force contact input and force contact output settings revert to
their default states.
FORCE CONTACT
OUTPUTS
FORCE Cont Op 1
: Normal
Range: Normal, Energized, De-energized, Freeze
FORCE Cont Op 2
: Normal
Range: Normal, Energized, De-energized, Freeze
FORCE Cont Op xx
: Normal
Range: Normal, Energized, De-energized, Freeze
On restart, the
TEST MODE FORCING
setting and the force contact input and force contact output settings revert to
their default states.
Содержание b30
Страница 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 50: ...2 36 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 208: ...4 86 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 441: ...CHAPTER 5 SETTINGS CONTROL ELEMENTS B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL 5 233 5 Figure 5 123 Time out mode ...
Страница 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 514: ...6 28 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 528: ...7 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 554: ...9 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL OUTPUT LOGIC AND EXAMPLES CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 600: ...A 16 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 608: ...C 6 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...