– 50 –
Fault Codes
Fault Code Display Mode
While the Zoneline is in the "OFF" mode, press and hold the FAN button with the AUX SET button
simultaneously to enter into this mode. The Zoneline will then display all active fault codes held in memory,
showing each one for 3 seconds on/o
Ⱥ
.
If no codes are present, display will show "--" and
À
ash that every 3 seconds on/o
Ⱥ
.
Displays all fault codes 3 times and then after 30 seconds more the Zoneline reverts to OFF mode. Pressing
AUX will clear stored faults but it will not exit the fault code menu. Any other button press takes Zoneline out
of this mode.
Fault Code
Number
Fault Meaning
E
ȹ
ect on operation
Z
hile fault
is ACTIVE
Fault reset
time
F1
Indoor fan fault - Fan motor not
moving at commanded speed
after 90 seconds of drive voltage.
No Resistance heating, fan, heat
pump or cooling available.
Fault clears
after 10
minutes.
F2
Outdoor fan fault - Fan motor
not moving at commanded
speed after 90 seconds of drive
voltage.
No heat pump or cooling
available. Resistance heating
and fan only.
Fault clears
after 10
minutes.
F3
External thermostat wiring
- Applied signal is not valid
and has been constant for 30
seconds.
No external control of fans,
heat or cooling. Internal control
operation only.
Clears once a
valid signal is
received.
F4
Indoor thermistor fault - One
of the indoor thermistors is not
reading valid temperatures. Valid
range is -10°F to 140°F.
No resistance heating, fan, heat
pump or cooling available. Fan
only.
Clears once a
valid signal is
received.
F5
Outdoor thermistor fault - One
of the outdoor thermistors is not
reading valid temperatures. Valid
range is -30°F to 140°F.
No cooling or heat pump
operation. Resistance heating or
fan only.
Clears once a
valid signal is
received.
(
Continued next page
)
Содержание AZ45E07DA Series
Страница 30: ...30 Service Main Board Service Main Board Continued next page...
Страница 53: ...53 Sealed System Refrigerant FloZ Cooling...
Страница 54: ...54 Sealed System Refrigerant FloZ Heating...