8
• Types and Ratings
2.
TYPES AND RATINGS
2.1
IEC Ratings
. Recommended Motor and Type Unit Ratings.
Light
Duty
Normal Duty (IEC Class 10)
Recommended Motor Ratings
Heavy Duty (IEC Class 20)
Recommended Motor Ratings
Type Unit
Max
Current
Rating
Current
rating
230V 400V
415V
480V
500V
575V 690V Current
rating
230V 400V
415V
480V
500V
575V 690V
A A kW
kW
kW
HP
kW A kW
kW
kW
HP
kW
8
8 2 3.0 4 5 5.5 8 1.5
3.0 4 5 5.5
QTx0008Uxxxx
17 17 4
7.5
7.5
15
15 12 3
5.5
5.5
10
8
QTx0017Uxxxx
34 31 8
15
18.5
15
22 31 8 15
18.5
25
22
QTx0031Uxxxx
54 44 11
22 30
40
37 44 11 22 30
40
37
QTx0044Uxxxx
65 58 15
30 37
50
55 55 15 30 37
50
45
QTx0058Uxxxx
72 72 22
37 45
60
55 66 18.5
37 45
60
55
QTx0072Uxxxx
104 85 22
45 55
75
75 80 22 45 55
75
75
QTx0085Uxxxx
130 105 30
55 55
100
90 99 30 55 55
100
90
QTx0105Uxxxx
156 145 45 75 90
150
132 130 37 55 90
125
90
QTx0145Uxxxx
170 170 55 90 110
150
160 134 37 75 90
125
132
QTx0170Uxxxx
248 210 55
110
132
200
200 203 55 110
132
200
200
QTx0210Nxxxx
361 310 90
160
200
300
250 310 75 160
200
300
250
QTx0310Nxxxx
390 390 110
200 250
300
355 344 110 160 250
350
315
QTx0390Nxxxx
480 460 132
250 315
450
400 432 132 250 315
450
400
QTx0460Nxxxx
480 460 132
250 315
450
400 432 132 250 315
450
400
QTx0460Uxxxx
610 580 160
315 400
500
560 488 160 250 355
500
400
QTx0580Nxxxx
610 580 160
315 400
500
560 552 160 315 400 560
QTx0580Uxxxx
820 650 200
355 400 630 552 160 315 400 560
QTx0650Nxxxx
820 820 250
400 560 800 690 200 400 500 710
QTx0820Uxxxx
1180 950 315
560 630 900 950 315 560 630 900
QTx0950Nxxxx
1375 1100 355 630 800 1000 1076 355 630 800 1000
QTx1100Nxxxx
1750 1400 400 800 1000
1400 400 800 1000
QTx1400Nxxxx
Note:
Select the appropriate ASTAT-XT, according to the main power supply and motor voltage rating.
Use QT1xxxx units for power supply and motors rated at 230V-500V
Use QT2xxxx units for power supply and motors rated at 460V-600V
Use QT3xxxx units for power supply and motors rated at 690V
1
Ratings in Amps. given for ambient temperature up to 40°C and 1000m altitude.
For higher ambient temperature between 40°C and 50°C, derate the current by 2.5% for each °C that is above 40°C.
2
Normal duty ratings, only IEC Class 10 protection is allowed.
3
Heavy duty ratings, IEC Class 10 and 20 protections are allowed.
Содержание ASTAT XT QT 0008U Series
Страница 1: ...GE Consumer Industrial ASTAT XT User Manual...
Страница 17: ...17 Technical Specifications 3 4 I O Wiring...
Страница 123: ...Ed 15 03 09 Copyright GE Power Controls 2009...