Step 1 - Preparation Cont.

Installation Instructions

Step 2 - Installation of the Indoor Unit

A. Select the Indoor location:

•  Do not expose the unit to unusual heat sources or steam 

outlets.

•  Select a location where there are no obstacles in front of 

the unit.

•  Make sure that condensate drainage can be conveniently 

routed away.

• Do not install near a doorway.

•  Ensure that the space around the left and right of the unit 

is more than 4”. The unit should be installed as high on the 
wall as possible but allow a minimum of 4” from the ceiling. 

•  Use a stud finder to locate and mark stud locations for 

mounting and to prevent unnecessary damage to the wall.

•  Install in a location that is strong enough to withstand the 

full weight and vibration of the unit.

•  Leave enough space to allow access for routine 

maintenance.

•  Select a location that gives easy access to removing and 

cleaning air filters.

•  Install in a location that is 3 ft. or more away from other 

electrical appliances, such as televisions and audio devices.

B. Install the Mounting Plate

•  Remove plastic bag, tape, and mounting plate from the 

back of the indoor unit.

•  Place the mounting plate on the wall in the desired location 

taking into account the minimum clearances necessary for 
proper operation.

•  Using a level, verify that the mounting plate is horizontal 

and mark the screw locations.

•  Attach the mounting plate to the wall with the supplied 

screws. 

•  Wall anchors are supplied if not able to align all screw holes 

with studs.

•  Be sure that the mounting plate has been attached firmly 

and that applied weight is evenly distributed by each 
screw. (At least one screw in wall stud, others can use wall 
anchors.)

•  The piping for the indoor unit may be routed to and from 

the unit in one of several directions: left, left rear, right, right 
rear, or right below. 

NOTES:

•  OD unit cannot hang from a ceiling or be stacked.

•  Ensure that accumulated snow, debris, etc… will not block the 

air inlet or the coil exchanger if installing the OD unit with a 
fence or rail guard around it.

•  Ensure ventilation in case of refrigerant leakage.  R-410A is a 

safe, nontoxic, and nonflammable refrigerant.

•  Avoid installing the OD unit where corrosive gases, such as 

sulfur oxides, ammonia, and sulfurous gas are produced.  If 
unavoidable, consult with an installation specialist about using 
a corrosion-proof or anti-rust additive to protect the unit coils.

•  Do not install the outdoor unit near the edge of a balcony. 

Otherwise, children may climb onto the outdoor unit and fall 
off of the balcony. 

•  Do not install the outdoor unit in the following areas: Areas 

heavily laden with oil or greasy vapors such as kitchens. Oils 
and grease will create sticky layer on the coil and also cause 
drainage problems, thus degrade unit performance.

•  Corrosive areas that can potentially have combustible 

gas leaks, contain suspended fibers or flammable dust, or 
flammables such as paint thinner or gasoline can cause fires. 

•  Areas that contain small animals, rodents, reptiles or insects 

that can infiltrate the equipment and cause damage to internal 
components.

•  Area where animals may urinate on the unit or ammonia may 

be generated. 

•  Install as necessary a protective fence or the like to prevent 

their access if the outdoor unit must be installed in an area 
within easy reach of the general public.

•  Take appropriate measures to protect it from those elements 

If the outdoor unit is installed in a cold region that is affected 
by snow accumulation, snow fall, or freezing. To ensure a 
stable operating, install inlet and outlet ducts.

•  Make sure the outdoor unit is installed level and is stable. 

Install snow protection hood as necessary. 

•  Avoid salty places such as the seaside for installation where 

air conditioner trouble is liable to occur.

•  Install the outdoor unit in a location that is away from exhaust 

or the vent ports that discharge vapor, soot, dust, or debris. 

•  Install the unit where it will not be tilted by more than 3°. 

However, do not install the unit with it tilted towards the side 
containing the compressor. 

•  When installing the outdoor unit where it may exposed to 

strong wind, fasten it securely. 

•  It is recommended that unit be installed under a canopy or 

elevated on a high stand. 

•  Protect the drain line from freezing in areas where 

temperature drops to 32°F (0°C) or lower. 

•  Please set up the outdoor unit in a high place and please 

do not arrange the frame of installed stand under the drain 
port, because the water dropped from the drain port repeats 
freezing and accumulating, and may block the drain port. 

•  Do not use mineral oils on flared parts. Prevent mineral oil 

from entering the refrigerant system. Introduction of mineral oil 
may reduce the system life. 

•  Be sure to use an inert gas such as nitrogen while brazing 

any refrigerant lines to prevent any oxidation 

•  Be sure not to exceed refrigerant tubing length limits for 

different models to ensure smooth operation of the unit. 
Otherwise the equipment life cannot be guaranteed.

Содержание ASH218JCDDA

Страница 1: ...panish version please visit GEAppliancesairandwater com L aspect peut varier selon le num ro de mod le Ce manuel d installation est uniquement imprim en anglais Pour la version fran aise ou espagnole...

Страница 2: ...age To receive a 10 year compressor and parts warranty registration is required within 60 days of installation ____________________________________ Model number ____________________________________ Se...

Страница 3: ...ndoor temperature to 68 F 20 C The indoor display will flash BP for five seconds and shut down automatically The system can now be used normally Note The automatic tests can also be by passed by setti...

Страница 4: ...ave been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the heat pump syst...

Страница 5: ...ve a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion valve or capillary tube may become blocked with contaminants Improper line sizing will degrade...

Страница 6: ...aring tool Hex wrench Hole saw 2 1 4 Insulation Refrigerant scale Level Manifold gauge set Measuring tape Micron gauge Mini split adapter 5 16 F to 1 4 M Nitrogen Pipe cutter PVC pipe Razor knife Ream...

Страница 7: ...k E 12k 12k E 7k 18k D 9k 18k D 12k 18k D THREE ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E Models that may require adapt...

Страница 8: ...k A B 1 D 2 24k A C 1 2 THREE ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k A C 1 2 7k 9k 24k A C 1 2 9k 9k 24k A C...

Страница 9: ...See Notes 1 and 2 Port E Required Adapter TWO ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1 2 24k A C 1 2 THREE ZONE 7k 7k 18k 7k 7k 24k A C 1 2 7...

Страница 10: ...7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18k 7k 7k 12k 24k A C 1 2 7k 7k 18k 18k 7k 7k 18k 24k A C 7k 9k 9k 9k E 7k 9k 9k 1...

Страница 11: ...2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k A C 1 2 7k 7k 9k 12k E 24k A C 1 2 7k 7k 7k 12k E 12k E 7k 7k 7k 12k E 18k...

Страница 12: ...t 28 700mm between the protection wall and the outdoor unit for air circulation to ventilate Install the outdoor unit in a place where water can drain Contact GEA Ductless for assistance if the above...

Страница 13: ...000 Above12 300 Above 40 1000 Above 177 4500 Above 24 600 If wall is half the height of the unit 8 250 If wall is between half the height of the unit and the same height of the unit 12 300 Select the...

Страница 14: ...coils Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony Do not install the outdoor unit in the following areas A...

Страница 15: ...e lower hooks engage the brackets see illustration Verify the unit is secured and flush to the wall Indoor Unit installation is finished at this time F Condensate Drainage Pipe Verify the condensate d...

Страница 16: ...iagram only demonstrates the wiring connection between outdoor indoor for dual zone as an example 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L2 to L2 ground to groun...

Страница 17: ...the wall bracket and where to cut the hole for piping NOTE Some models may not have a cardboard template in this case a manual measurement is needed to determine the piping hole location When mounting...

Страница 18: ...poor terminal connections C Electrical Connections for the Outdoor Unit WARNING RISK OF ELECTRIC SHOCK Could cause injury or death Make sure power is off before touching wires NOTE Be certain all wiri...

Страница 19: ...ply L1 to L1 L2 to L2 Outdoor Unit Indoor Unit A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red Green...

Страница 20: ...B Indoor unit C Indoor unit D 3 2 1 N L C 3 2 1 N L C 3 2 1 N L C Strain Relief Brackets E 3 2 1 N L C Model Number Factory Charge Total Pipe Length of factory charge Additional charge rule Branch Ma...

Страница 21: ...ining refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion Refrigerant when used as a trace gas should only be mixed with d...

Страница 22: ...move the cap from the liquid line valve Using a hex wrench open the valve then replace and tighten the cap securly to avoid leaks Remove the cap from the suction line valve Using a hex wrench open the...

Страница 23: ...g or removing the remote controller from the remote control holder cleaning methods precautions for operation etc Review precautions for operation Recommend that the user read the Operating Instructio...

Страница 24: ...been maintained annually by a licensed HVAC technician proof required Damage caused by a used or unapproved component or part by GE Appliances a Haier company e g a used and or unapproved condenser a...

Страница 25: ...of a new building but subsequent purchases will receive the remainder of the Standard Base Warranty The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies This...

Страница 26: ...26 31 5000560 Rev 5 Notes...

Страница 27: ...LIRE ATTENTIVEMENT CONSERVEZ CES INSTRUCTIONS Instructions d installation Multizone sans conduit avec unit s int rieures murales hautes 31 5000560 Rev 5 11 22 GEA...

Страница 28: ...jours suivant l installation ASH218JCDDA ASH324JCDDA ASH436JCDDA Cooling 14 F to115 F Heating 4 F to 75 F ASH220NCDDA ASH324NCDDA ASH436NCDDA ASH542JCDDA Cooling 14 F to115 F Heating 15 F to 75 F NOTE...

Страница 29: ...mode d int rieur au mode Dry en premier puis r glez la temp rature int rieure 20 C 68 F BP clignotera sur l afficheur int rieur pendant cinq seconds puis s teindra automatiquement Le syst me peut mai...

Страница 30: ...es renseignements dans ce manuel doivent tre observ s afin de minimiser le risque d incendie de d charge lectrique ou de blessure Utilisez cet quipement uniquement aux fins auxquelles il est fait ment...

Страница 31: ...Un dimensionnement incorrect de la tuyauterie va diminuer le rendement Les pointes de pression du r frig rant R410A sont beaucoup plus lev es que celles du R22 Utilisez une tuyauterie en cuivre dont l...

Страница 32: ...A Cl hexagonale Scie cloche 2 1 4 po Isolant Balance de r frig rant Niveau Manom tre de pression d admission d finir Ruban mesurer Microvacuom tre Adaptateur mini split 5 16 po F 1 4 po M Azote Coupe...

Страница 33: ...k E 7k 18k D 9k 18k D 12k 18k D TROIS ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E 0RGqOHV SRXYDQW QpFHVVLWHU GHV DGDSWDWH...

Страница 34: ...8k D 18k 24k A B 1 D 2 18k 24k A B 1 D 2 24k A C 1 2 TROIS ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k A C 1 2 7k...

Страница 35: ...urs varient pour mod le 24K Voir notes 1 et 2 Orifice E Adaptateur requis DEUX ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1 2 24k A C 1 2 TROIS Z...

Страница 36: ...UATRE ZONE 7k 7k 7k 7k E 7k 7k 7k 9k E 7k 7k 7k 12k E 7k 7k 7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18k 7k 7k 12k 24k A C 1...

Страница 37: ...7k 7k 9k E 12k E 7k 7k 7k 9k E 18k 7k 7k 7k 7k E 24k A C 1 2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k A C 1 2 7k 7k 9k...

Страница 38: ...p ex pr s de b timents etc o elle peut tre prot g e de la brise marine qui peut l endommager rigez un mur de protection autour de l unit pour bloquer la brise marine s il est impossible d viter d inst...

Страница 39: ...neige ou du vent Installez un coupe vent pour prot ger l unit contre le vent 3 Installation and maintenance space Selection of installation location of outdoor Above 12 300 Above 40 1000 Above 16 400...

Страница 40: ...dditifs qui r sistent la corrosion ou la rouille afin de prot ger les serpentins de l unit N installez pas l unit ext rieure pr s du bord d un balcon Autrement les enfants peuvent grimper sur l unit e...

Страница 41: ...r de d charge de traction Replacez les deux plaques de recouvrement et abaissez l enveloppe frontale une fois les connexions au bornier termin es eWDSH QVWDOODWLRQ GH O XQLWp LQWpULHXUH 6XLWH Plaque d...

Страница 42: ...llustre seulement les connexions entre les unit s int rieure et ext rieure dans le cas d une zone double titre d exemple 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L...

Страница 43: ...yauterie REMARQUE Le gabarit en carton n est pas fourni avec certains mod les Il faudra alors effectuer manuellement les mesures afin de d terminer l emplacement du trou pour la tuyauterie Pendant le...

Страница 44: ...aque est serr e Assurez vous que le c ble torsad 14 4 est fix sous la ferrure serre c ble Assurez vous que toutes les connexions sont solides REMARQUE L omission de suivre les directives de c blage pe...

Страница 45: ...0 volts L1 L1 L2 L2 Unit ext rieure Unit int rieure A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red...

Страница 46: ...ASH324JCDDA 67 100 82 197 ASH436JCDDA 90 131 82 230 ASH220NCDDA 69 66 82 165 ASH324NCDDA 82 100 82 197 ASH436NCDDA 102 131 82 230 ASH542JCDDA 113 164 82 262 Instructions d installation eWDSH QVWDOODWL...

Страница 47: ...tez une fuite effectuez la r paration des raccords et faites un nouveau contr le Continuez si n avez pas d tect de fuite pendant 3 minutes En utilisant le m me r servoir r gulateur chargez le syst me...

Страница 48: ...de recharge si aucune tiquette n est pr sente Retirez le couvercle de la valve de la tuyauterie de liquide l aide d une cl hexagonale ouvrez la valve puis remettez et ajustez le couvercle Retirez le...

Страница 49: ...pr cautions d utilisation Nous recommandons que l usager lise attentivement les Instructions d utilisation 7HVW GX V VWqPH Veuillez expliquer au client comment faire fonctionner le syst me en utilisa...

Страница 50: ...ent ou de conditions similaires Un Produit qui n a pas t install ou r par par un technicien agr en chauffage ventilation et climatisation La main d uvre et les services connexes pour la r paration ou...

Страница 51: ...mplacement de tout autre recours Cette garantie ne couvre pas les dommages accessoires ou indirects Certains tats ou provinces ne permettent pas l exclusion des dommages accessoires ou indirects donc...

Страница 52: ...52 31 5000560 Rev 5 Notes...

Страница 53: ...LEA CUIDADOSAMENTE GUARDE ESTAS INSTRUCCIONES Instrucciones de instalaci n Multizona sin ductos con unidades interiores de pared alta 31 5000560 Rev 5 11 22 GEA...

Страница 54: ...encuentran en la etiqueta del lado de la bomba de calor as como la fecha de compra Adjunte su comprobante de compra a este manual para ayudarlo a obtener el servicio de garant a si es necesario Para...

Страница 55: ...68 F 20 C En la pantalla interior parpadear BP durante cinco segundos y sta luego se apagar de forma autom tica El sistema se podr usar ahora de forma normal Nota Las pruebas autom ticas tambi n se po...

Страница 56: ...zar un servicio que requiere el ingreso al sistema de refrigeraci n sellada las regulaciones federales requieren que el trabajo sea realizado por un t cnico que posea una certificaci n Clase II o Univ...

Страница 57: ...inadecuado reducir el rendimiento La presi n m xima de R410A es muy superior a R22 Use una tuber a de cobre con el grosor de pared adecuado A fin de evitar la rotura de la tuber a evite realizar curva...

Страница 58: ...llador Phillips n 2 Taladro Abocardador de 45 Llave Hexagonal Sierra de Agujero de 2 1 4 Aislante Nivel Calibrador de Colector Cinta de Medici n Medidor de Micrones Adaptador para Mini Split 5 16 H a...

Страница 59: ...k D 12k 18k D TRES ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E Modelos que pueden requerir adaptadores 1 Estos modelos 24...

Страница 60: ...4k A C 1 2 18k D 18k 24k A B 1 D 2 18k 24k A B 1 D 2 24k A C 1 2 TRES ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k...

Страница 61: ...adores var an en relaci n al Modelo de 24K Lea las Notas 1 y 2 Adaptador requerido del puerto E DOS ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1...

Страница 62: ...uerido del puerto E CUATRO ZONE 7k 7k 7k 7k E 7k 7k 7k 9k E 7k 7k 7k 12k E 7k 7k 7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18...

Страница 63: ...7k 9k E 9k E 7k 7k 7k 9k E 12k E 7k 7k 7k 9k E 18k 7k 7k 7k 7k E 24k A C 1 2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k...

Страница 64: ...n un lugar tal como edificios cercans etc donde se encuentre protegida de la brisa del mar la cual podr da ar la misma Si no es posible evitar la instalaci n de la unidad exterior cerca de la costa ma...

Страница 65: ...nstale un deflector de viento para evitar la exposici n a este ltimo 3 Installation and maintenance space Selection of installation location of outdoor Above 12 300 Above 40 1000 Above 16 400 Above 16...

Страница 66: ...aditivos a prueba de corrosi n y antioxidantes para proteger las bobinas de la unidad No instale la unidad externa cerca del extremo de un balc n De otro modo los ni os podr n trepar sobre la unidad e...

Страница 67: ...s protectoras y baje la carcasa frontal una vez completado el cableado del bloque terminal C Instale el Agujero de la Tuber a Siempre use tuber as de cobre nuevas y limpias Nunca vuelva a usar una tub...

Страница 68: ...exi n del cableado entre interior y exterior para zona dual 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L2 to L2 ground to ground C 3 L 2 N 1 A t i n U r o o d n I C...

Страница 69: ...ara la tuber a NOTA Es posible que algunos modelos no cuenten con una plantilla de carb n en este caso ser necesaria una medici n manual para determinar la ubicaci n del agujero de la tuber a Al monta...

Страница 70: ...e el suministro de voltaje de este sistema sea el correcto Conecte el cableado de la fuente de alimentaci n y el cableado interno usando un soporte para cables conductores sobre el lado de la unidad d...

Страница 71: ...ios L1 a L1 L2 a L2 Unidad exterior Unidad interior A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red...

Страница 72: ...L C 3 2 1 N L C Strain Relief Brackets E 3 2 1 N L C Informaci n de Carga de Refrigerante y Longitud de la Tuber a N mero de Modelo Carga de F brica Longitud Total de la Tuber a con carga de f brica R...

Страница 73: ...ice un control de p rdidas en los accesorios abocinados usando burbujas de jab n u otro dispositivo de detenci n Si una p rdida es detectada realice las reparaciones de los accesorios y vuelva a hacer...

Страница 74: ...as unidades exteriores Si no encuentra el adhesivo escriba las cantidades en la unidad exterior con un marcador indeleble sobre el puerto de carga Retire la tapa de la v lvula de la tuber a de l quido...

Страница 75: ...e uso Recomendamos que el usuario lea las Instrucciones de uso detenidamente Prueba del Sistema Por favor expl quele al cliente c mo utilizar el sistema usando el Manual del Propietario el cual se enc...

Страница 76: ...ctrica incorrecta Da o resultante de inundaciones incendios viento iluminaci n accidentes o condiciones similares Un producto que no fue instalado o su servicio t cnico no fue realizado por un t cnico...

Страница 77: ...garantizada en lugar de todas las dem s soluciones Esta garant a no cubre da os incidentales o consecuentes Algunos estados y provincias no permiten la exclusi n de da os incidentales o consecuentes...

Страница 78: ...78 31 5000560 Rev 5 Notas...

Страница 79: ...31 5000560 Rev 5 79 Notas...

Страница 80: ...Not Return This Product To The Store If you have a problem with this product please call 1 844 487 9443 for the name and telephone number of the nearest authorized service center DATED PROOF OF PURCH...

Отзывы: