background image

24

Consumer 

Support

Troubleshooting 

Tips

Care 

and 

Cleaning

Operating 

Instructions

Safety 

Instructions

Normal Operating Sounds

You may hear a pinging noise caused by water being 

picked up and thrown against the condenser on rainy 

days or when the humidity is high. This design feature 

helps remove moisture and improve efficiency.

You may hear relays click when the controls cycle  

on and off or are adjusted to change the room 

temperature.

Water will collect in the base pan during high humidity 

or on rainy days. The water may overflow and drip 

from the outdoor side of the unit.

The indoor fan runs continuously when the unit is 

operating in the cooling mode, unless the fan switch 

behind the case front panel is set at fan cycle (up).  

This will cause the fan to cycle on and off with  

the compressor. You may also hear a fan noise  

stop and start.

You may notice a few minutes delay in starting  

if you try to restart the Zoneline too soon after  

turning it off or if you adjust the thermostat right after 

the compressor has shut off. This is due to a built-in 

restart protector for the compressor that causes  

a 3-minute delay.

During the defrost cycle, both indoor and outdoor  

fans stop and the compressor will operate in the 

cooling mode to remove frost from the outdoor coil. 

After defrost, the unit will restart in electric heat to 

quickly warm the room to the desired comfort level.

To protect the compressor and prevent short cycling, 

the unit is designed to run for a minimum of 3 minutes 

after the compressor starts at any thermostat setting.

Things that are normal.

 

3-Minute

 

Delay

“CLICK”

S

I

L

E

N

C

E

COMPRESSOR 

PROTECTION

Содержание Appliances Zoneline 8500 series

Страница 1: ...and Heat Pump Models 8500 Series Owner s Manual and Installation Instructions GEAppliances com Zoneline Vertical Printed in China Write the model and serial numbers here Model ________________________...

Страница 2: ...th or at either the plug or connector end n Product must be operated with the electrical plug supplied with the product Do not replace the electrical plug supplied with the product n If the receptacle...

Страница 3: ...if present NOTE The owner is responsible for setting the appropriate dip switches and connecting terminals Controls Dip Switches Dip Switches All Electric Heat Heat pump models only When this switch i...

Страница 4: ...usly Occupancy Sensor Field Supplied When this switch is enabled UP it allows the unit to utilize an infrared motion sensor and a door switch for occupancy detection This feature combined with field d...

Страница 5: ...to select the cooling limits The next three switches are used to control the heating limits Temperature limiting during COOL mode all temperatures shown in F UP DOWN Minimum Maximum NONE 1 2 3 60 85 1...

Страница 6: ...Zoneline operation No common busing is permitted A separate wire pair must be run from each separate controlling switch to each individual Zoneline Room Air Sensor Requires room air sensor kit RAVRMS...

Страница 7: ...ogether to automatically cycle the unit between normal and energy management operations Central Desk Control When connected the unit lock out is released and it can be turned ONor OFF with a switch lo...

Страница 8: ...ructions Other features of your Zoneline About Heat Pumps on some models Heat pumps can reduce operating costs by exchanging heat from the outside air even when the outside temperature is below freezi...

Страница 9: ...e filter at least every 30 days Air Filters The most important thing you can do to maintain the Zoneline is to change the filter at least every 30 days Dirty filters reduce cooling heating and air flo...

Страница 10: ...led by a qualified electrician Follow the National Electrical Code NEC and or local codes and ordinances For personal safety this Zoneline unit and case must be properly grounded Protective devices fu...

Страница 11: ...ordance with the NEC and local codes ordinances and regulations Power supply kit Recommended branch circuit wire sizes Nameplate maximum circuit AWG Wire breaker size size 15A 14 20A 12 30A 10 AWG Ame...

Страница 12: ...TION CHART on page 13 to select the appropriate kit It is the responsibility of the installer to ensure the connection of components is done in accordance with electrical codes Direct connection to br...

Страница 13: ...240 VAC When connecting the Zoneline to a single phase circuit for 230V applications Connect the white and black leads of the Zoneline power supply kit to the branch circuit L1 and L2 leads The white...

Страница 14: ...12 D x 193 4 W x 32 H RAVWP15 15 D x 193 4 W x 32 H Cutout Dimensions 20 W x 321 4 H Access Panel with Return Air Grille RAVRG1 Return Air Grille RAVRG2 Cutout Dimensions 28 W x 48 H Cutout Dimensions...

Страница 15: ...Filter bracket Secure platform to the floor Platform 231 4 x 231 4 square Min load capacity 175 lbs 4 min from front of case Unit installed through FRONT of case 5 min from front of case Unit installe...

Страница 16: ...epth 231 8 D Case height 31 E Condensate drains 3 4 connector Primary Drain Centerline of cutout is approximately 51 4 from left case wall and 81 2 from back case wall Secondary Drain Centerline of cu...

Страница 17: ...the option that best suits your installation requirements Follow the Installation Instructions provided with the return air grille accessory for installation details NOTE Use only one filter in the in...

Страница 18: ...4 W x 32 H RAVWP12 12 D x 193 4 W x 32 H RAVWP15 15 D x 193 4 W x 32 H 2 Make drain hole cutout s Primary Drain Centerline of drain is approximately 51 4 from left platform edge and 81 2 from back pl...

Страница 19: ...Flex duct can collapse and cause airflow restrictions Do not use flex duct for 90 bends or unsupported runs of 5 ft or more 3 Installation Instructions Your airflow should be balanced based on many f...

Страница 20: ...the unit to be slid into the case 2 Ground the unit to the case by installing the front case to unit hex bolt and discard the two case to unit side screw 5a Hex bolt Air discharge outlet Rigid ductwo...

Страница 21: ...tions as appropriate of this manual for proper connections 3 Replace the case front panel by replacing the four front screws and the two top screws 6 Installation Instructions Thermostat Unit Connecti...

Страница 22: ...at connections 3 Raise the top duct by turning all four case top duct adjusting screws counterclockwise 4 Remove the front and or side case to unit grounding screw if present 5 Slide the unit out of t...

Страница 23: ...ve a minimum of 65 free area Non GE grilles may be too restrictive for proper performance Consult your salesperson for assistance The air filter is dirty Change the filter at least every 30 days See t...

Страница 24: ...el is set at fan cycle up This will cause the fan to cycle on and off with the compressor You may also hear a fan noise stop and start You may notice a few minutes delay in starting if you try to rest...

Страница 25: ...Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support Notes GEAppliances com 25...

Страница 26: ...Notes 26 Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions...

Страница 27: ...and you may also have other rights which vary from state to state or province to province To know what your legal rights are consult your local state or provincial consumer affairs office or your stat...

Страница 28: ...t our Website today For the hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories GEAppliances com Individuals qualified to service their own appliances can have parts or access...

Отзывы: