DEH-41473
AKD-20 AR / Entellisys AR Low-voltage Switchgear
Section 4. Equipment Installation
©2016 General Electric. All rights reserved.
24
Figure 4.3 Indoor enclosure floor plan and cable entry space (inches)
Table 4.1 Indoor enclosure depth, cable direction, and cable space (inches)
Section Width
“W”
Section Depth
“D”
Front
Compartment
“FC”
Horizontal Bus
Rating
(Amperes)
Cable Direction
(Note 4)
Cable Space
“X”
AKD-20 AR
Only
“N1”
Entellisys AR
Only
“N2”
22, 30, 38
54
33
4,000 & Below Below
16
9
10.25
Above
20
60
33
4,000 & Below Below
22
Above
26
40
5,000 & Below Below
15
Above
19
67
33
4,000 & Below Below
29
Above
33
40
5,000 & Below Below
22
Above
26
74
33
4,000 & Below Below
36
Above
40
40
5,000 & Below Below
29
Above
33
Note 1: Offset ground bus.
If greater than 6 ground lugs are required in the
same section, an offset ground bus is provided.
When the offset ground bus and cable entry is
located both bottom or above, it will reduce the
available cable space.
Note 2: Neutral Bus (Optional)
(AKD-20 AR Only)
.
When this option is provided and the neutral bus
and cable entry is located both bottom or top, it will
reduce the available cable space.
Note 3: Neutral Bus (Optional)
(Entellisys AR Only)
.
When this option is provided and the neutral bus
and cable entry is located both bottom or top, it will
reduce the available cable space.
Note 4: Cable Direction Below.
If the section does not have a circuit breaker in the
“D” compartment, an additional 4 inches of cable
space is available.
General:
Secondary control lead space may be
required on left, right, or both sides of cable
compartment. Consult factory drawings for details.