[26]
Precise stop inverse (on-
ly terminal 33)
Prolong the stop signal to give a precise stop independent of scan time. The function is available for terminal 33 only.
[27]
Start, precise stop (only
terminal 33)
As [26], but including Start.
[28]
Catch up
Select Catch up/Slow down to increase or reduce the resulting reference value by the percentage set in par. 3-12.
[29]
Slow down
Same as Catch up [28]
[32]
Pulse input (only termi-
nal 33)
Select Pulse input when using a pulse sequence as either reference or feedback. Scaling is done in par. group 5-5*.
[34]
Ramp bit 0
Logic 0 = Ramp1, see par. 3-4*.
Logic 1 = Ramp2, see par. 3-5*.
[60]
Counter A (up)
Input for counter A.
[61]
Counter A (down)
Input for counter A.
[62]
Reset counter A
Input for reset of counter A.
[63]
Counter B (up)
Input for counter B.
[64]
Counter B (down)
Input for counter B.
[65]
Reset counter B
Input for reset of counter B.
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
*
Start
Select function from available digital input range.
See par. 5-1* for choices.
5-11 Terminal 19 Digital Input
Option:
Function:
[10]
*
Reversing
Select function from available digital input range.
See par. 5-1* for choices.
5-12 Terminal 27 Digital Input
Option:
Function:
[1]
*
Reset
Select function from available digital input range.
See par. 5-1* for choices.
5-13 Terminal 29 Digital Input
Option:
Function:
[14]
*
Jog
Select function from available digital input range.
See par. 5-1* for choices.
5-15 Terminal 33 Digital Input
Option:
Function:
[16]
*
Preset bit 0
Select function from available digital input range.
See par. 5-1* for choices.
4.6.3. 5-4* Relays
Parameter group for configuring timing and output functions for relays.
[0]
No Operation
Default for all digital and relay outputs.
[1]
Control Ready
Control board receives supply voltage.
[2]
Drive Ready
Frequency converter is ready for operation and applies supply signal on control board.
[3]
Drive Ready, Remote
Frequency converter is ready for operation in Auto mode.
[4]
Enable/No Warning
Frequency converter is ready for operation. No start or stop command is given. No warnings are present.
[5]
Drive Running
Motor is running.
[6]
Running/No Warning
Motor runs, and no warning are present.
AF-60 LP™ Micro Drive Programming Guide
33
4