Module Specifications
Power Requirements
Input Power
+5 VDC ±5% from 90-30 backplane
Power consumption
300mA typical, 400mA maximum
Environmental Requirements
Operating Temperature Range
0°C to 55°C
Storage Temperature Range
-45°C to 85°C
Operating Humidity Range
5% to 95% non-condensing
Ventilation
Convection
Vibration
IEC68-2-6, JISC0911
1G at 40—50 Hz, 0.012p-p at 10—40 Hz
Shock
IEC68-2-27, JISC0912 15G, 11ms
Flammability
PCB material UL-94VO
Components UL recognized
ESD Immunity
IEC801-2, 8KV air discharge, 4.4KV contact discharge.
RF Susceptibility
IEC801-3
10V/meter
Fast Transient Susceptibility
IEC801-4, 1 KV specification
Electrical Surge Susceptibility
ANSI/IEEE C37.90 or IEC801-5
ANSI 37.90a
IEC801.5
Agency Approvals
CSA 22.2 213-M1987 Hazardous Location
UL 1604 with C-UL Hazardous Location
CSA 22.2 142-M1987 Process Control
UL 508 Industrial Control Equipment
CISPR11, EN55011, Class A
FCC Part 15, Subpart J Class A limits